3.3. LCD SETTINGS CONFIGURATION
There are 9 UPS settings that can be configured by the user.
1. Press the " E NTER " button simultaneously for 5 seconds to activate the setting
mode.
The first configuration parameter will be displayed on the LCD screen.
Note: The manual settings programming mode can ONLY be invoked while UPS is in
Bypass mode or Standby mode. To make UPS on Standby mode or Bypass
mode, connect utility power to UPS and do not turn on UPS.
2. Press the " E NTER " button to select the setting you want to configure.
3. Press the " E NTER " buttons to scroll through the different parameters and select
the parameter you want.
4. Press the " E SC " button for 5 seconds to cancel and exit setting mode. Press the
" E NTER " button for 5 seconds to save all the settings you just do and exit setting
mode.
5. In any mode(Except setting mode), Press the " E SC " button simultaneously for 5
seconds to disable and enable buzzer alarm
Setting
Configure
item
Submenu
Output
001
Voltage
Output
002
Frequency
003
ECO Mode *
Bypass Mode
004
**
Available Settings
=[208V] [220V][230V]
[240V]
= [50Hz][60Hz]
[0%] (Disable) [10%][15%]
(Enable)
[DIS] (Disable) [ENA]
(Enable)
ON-LINE 1000VA / 2000VA / 3000VA
Default
LCD Display
Setting
230V
50Hz
0%
Enable
P H 9210 - PH 9220 - PH 9230 .
52 / 58