Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Loss
EN
Low Line Comeback
Voltage
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Transfer
Inverter
Time
Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Type
Numbers
Standard
Recharge Time
Model
Charging Current
Charging Voltage
Type
Numbers
Long-run
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension, D X W X H
mm
Outline
Net Weight (kgs)
Dimension, D X W X H
mm
Packaging
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Derate capacity to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
10000
10000L
10000VA / 9000W
Battery
Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
ECO
> 89%
> 86%
12 V / 9 Ah
20(18-20 adjustable)
1.0 A ± 10% (max.)
4.0 A ± 10% (max.)
815X250
592X250
X826
109
920X380
700X385
X1025
127
Less than 60dB @
1 Meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
15000
15000L
15000VA / 13500W
110 VAC(Ph-N) ± 3 % at 50% Load
176 VAC(Ph-N) ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC(L-N) ± 3 % at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Three phase with Neutral
≧ 0.99 at 100% Load
Three Phase with Neutral
208/220/230/240VAC(Ph-N)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
>89%
>88%
12 V / 9 Ah
2 x 20(18-20 adjustable)
9 hours recover to 90% capacity
2.0 A ± 10% (max.)
273 VDC ± 1%
Depending on applications
4.0 A ± 10% (max.)
273 VDC ± 1%
815X250
592X250
X826
X826
X826
38
164
40
920X380
700X385
X1071
X1025
X1071
45
182
47
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
Power management from SNMP manager and web browser
33
20000
20000L
20000VA / 18000W
± 1%
3:1 max
0 ms
<10 ms
>89%
>87%
12 V / 9 Ah
2 x 20(18-20 adjustable)
2.0 A ± 10% (max.)
18 - 20
4.0 A ± 10% (max.)
815X250
592X250
815 X 300 X
X826
X826
164
40
920X380
700X385
920 X 430 X
X1025
X1071
182
47
<1000m
Less than 65dB @ 1 Meter
30000
30000L
30000VA / 27000W
>90%
>89%
12 V / 9 Ah
3 x 20(18-20 adjustable)
4.0 A ± 10% (max.)
12.0 A ± 10% (max.)
815X250
1000
X 826
233.5
64
920X380
1205
X 1025
250.5
90
Tabla de contenido
loading

Tabla de contenido