PowerWalker VFI 10000CP 3/3 Manual De Instrucciones página 24

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

03: Voltage range for bypass
Interface
EN
04: Frequency range for bypass
Interface
05: ECO mode enable/disable
Interface
06: Voltage range for ECO mode
Interface
07: Frequency range for ECO mode
Interface
08: Bypass mode setting
Interface
Setting
Parameter 2: Set the acceptable low voltage for bypass. Setting
range is from 110V to 209V and the default value is 110V.
Parameter 3: Set the acceptable high voltage for bypass. Setting
range is from 231V to 276V and the default value is 264V.
Setting
Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3: Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
Setting
Parameter 3: Enable or disable ECO function. You may choose
following two options:
DIS: disable ECO function
ENA: enable ECO function
If ECO function is disabled, voltage range and frequency range for
ECO mode still can be set, but it is meaningless unless the ECO
function is enabled.
Setting
Parameter 2: Low voltage point in ECO mode. The setting range
is from -5% to -10% of the nominal voltage.
Parameter 3: High voltage point in ECO mode. The setting range
is from +5% to +10% of the nominal voltage.
Setting
Parameter 2: Set low voltage point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3: Set high voltage point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
Setting
19
Tabla de contenido
loading

Tabla de contenido