Endress+Hauser RIA 550 Manual De Utilización página 33

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 76
Operation matrix
Address
identifier
PROG
Select programme
RANG
Set up range
DIM
Set up engineering units
FILT
Set up filter time (deep pass)
DP
Set up decimal point
SCLO
Lower range point
SCHI
Upper range point
BGLO
Lower bargraph zoom
BGHI
Upper bargraph zoom
MODE
Set up relay mode *
SP
Limit set point (for relay) *
HYST
Limit hysteresis (relay return) *
PRES
Do preset
TEST
Run test function
DINT
Set up display view angle
CALF
Release calibration
* = Example:
Mode selection is MAX, SP is set to 150, HYST is set to 10,
relay de-energises on value above 150 and energises at 140.
Meaning
1 =
2 =
4-20
0-20
0-1V
0-10
OFF
0..9999 seconds
0.000
00.00
000.0
0000
-999 .. 9999
-999 .. 9999
-999 .. 9999
-999 .. 9999
OFF
MIN
MAX
OC
-999 .. 9999
-999 .. 9999
NO
YES
NO
YES
1..16
NO
YES
Process display
Setting up possibilities
One or two channel display (standard)
Delta function: channel 1 - channel 2
Delta is displayed in channel 2 and all
limit functions are active on the delta
function. Addresses DIM and DP are auto-
matically transferred to channel 2.
Delta function is indicated in display as (∆)
4-20 mA with open circuit monitor (—)
0-20 mA
0-1 V
0-10 V
No units
2 units available see next page
3 decimal points
2 decimal points
1 decimal point
No decimal point
Relay inactive
Relay in "minimum security" de-energises
when value is below set point, on power
failure or unit fault
Relay in "maximum security" de-energises
when value exceeds set point, on power
failure or unit fault
Relay de-energises on cable open
circuit, on power failure or unit fault
Load standard settings
Control all display segments and relays
16 = horizontal view; 1 = view from below
Lock calibration
Release calibration CALR
31
Tabla de contenido
loading

Tabla de contenido