Priming The Pump - Riello Burners 40 Serie Instrucciones Para La Instalación, Uso Y Mantenimiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

OIL LINES
Warning: before starting the burner make sure that the return pipe-line is not clogged: any
obstruction would cause the pump seals to break.
WARNING
The pump is supplied for use with a two pipe system.
For use on a one pipe system, it is necessary to remove the by-pass
screw (A), (see figure).
D5219
H = Difference of level.
L = Max. length of the
suction line.
I.D.= Internal diameter of the
oil pipes.
D5220
A filter must be installed on the suction fuel line.
2341
H
meters
0.5
1
1.5
2

PRIMING THE PUMP

Loosen the plug of the vacuum gauge (5, fig. 1,
page 1) and wait until the fuel flows out.
L meters
H
I. D.
I.D.
meters
8 mm
10 mm
0
35
100
0.5
30
100
1
25
100
1.5
20
90
2
15
70
3
8
30
3.5
6
20
3
GB
L meters
I. D.
I.D.
8 mm
10 mm
10
20
20
40
40
80
60
100
The pump vacuum should not exceed
a maximum of 0.4 bar (30 cm Hg).
Beyond this limit gas is released from
the oil.
Oil lines must be completely air-
tight. The return line should termi-
nate in the oil tank at the same level
as the suction line; in this case a
non-return valve is not required.
When the return line arrives over the
fuel level, a non-return valve must be
used.
This solution however is less safe than
previous one, due to the possibility of
leakage of the valve.
PRIMING THE PUMP
Start the burner and wait for the prim-
ing. Should lock-out occur prior to the
arrival of the fuel, await at least 20 sec-
onds before repeating the operation.
A
D5199
Tabla de contenido
loading

Este manual también es adecuado para:

40 g3431t13743112

Tabla de contenido