Installation
Planning before installation
Install the unit to a position where any danger to the UPS is minimized to ensure a
long service life:
•
Install the UPS indoors.
•
Leave 50cm of space on each side of the cabinet to enable cooling airflow and
ensure that the circulation of air to the ventilation slits is not obstructed.
•
Avoid excessively high temperature and excessive moisture
•
Make sure that the surface is solid and flat
Rack mount installation – requires rack mounting kit, to be purchased
separately
•
Identify the rail holes in the rack for positioning the cabinet. Position the rails in
the bottom of the 3U space for 6kVA units and 5U space for 10kVA units.
•
Slide the cabinet into the rack. (Fig.1)
•
If installing additional UPS units, repeat the steps above for each cabinet
Tower installation
PowerValue 11 RT 6 kVA
•
Carefully rotate the LCD control panel 90º to the right. (Fig.2)
•
Place the units to a vertical position.
•
Screw the supports to the sides of the unit. (Fig.3)
PowerValue 11 RT 10 kVA
•
Carefully rotate the LCD control panel 90º to the right in the top and bottom front
panels. (Fig.4)
•
Place the units to a vertical position.
•
Screw the supports to the sides of the unit. (Fig.5)
Quick guide | PowerValue 11 RT 6-10 kVA 13