Boiler ignit. dynamic
Boiler switching off
dynamic
T-reset
On modulat. value
Min modulation value
Min modul value
AC modulation value
(GC) Sequence1
(GC) Sequence2
Next mode
Time sequen. change
Idle time
00min-30 min
Leave value with F key [end]
20-500 K
100K
20-500 K
100K
5-500
50
50%-100%
80%
10%-60%
30%
00%-60%
30%
40%-100%
80%
-
1 2 3 4 5 6 7 8
-
8 7 6 5 4 3 2 1
Sequence1
Sequence2
Timed
1
1/2 switch
Rotating
Sorting
0-800 hrs
0 hrs
00min
Modulation dynamics parameter; best to leave default value
20
Modulation dynamics parameter
Modulation dynamics parameter; best to leave default value
Previous module value to connect next module
Minimum modulation value module disconnection; not
15
possible to set parameter <15%
Modulation minimum value required to activate next module
Modulation rated value for modules (with AC values only –
not cascade – do not touch)
Cannot be changed
Cannot be changed
Switchover order in sequence 1
Switchover order in sequence 2
Switchover between sequence 1 and 2 according to number
hrs. in service (change time)
For 2 modules with different capacity: lowest number of
modules activated to satisfy request
Change time up, 1st boiler in the cascade active sequence
becomes the last
Change in succession of 1st generator based on n. working
hrs. after change time
SELECT Sequence change time
Waiting time before connecting/disconnecting module
(00=10sec)
CUT THE JUMPER
7
EN
fi g. 4