Web Server Configuration - Grundfos CIM 500 Instrucciones De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Web server configuration

The built-in web server offers easy monitoring of the
CIM 500 module and makes it possible to configure
functions and Industrial Ethernet protocols.
By means of the web server you can also update the
firmware of the CIM 500 module and store/restore
settings.
To connect a PC to the CIM 500, proceed as follows:
1. Connect the PC and the module, using an Ether-
net cable.
2. Configure the Ethernet port of the PC to the
same network as the CIM 500, e.g.
192.168.1.101. See section How to configure an
IP address on your PC.
3. Open a standard Internet browser and
type 192.168.1.100 in the URL field.
4. Log in to the web server.
Username
admin (default)
Password
Grundfos (default)
Login
Fig. 7
Login
Object
Description
Enter username. Default: admin.
Username
You can change the username via the User Management web page. See page 19.
Enter password. Default: Grundfos.
Password
You can change the password via the User Management web page. See page 19.
12
Tabla de contenido
loading

Tabla de contenido