Troubleshooting Guide - Far Tools GG 4500 Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

TROUBLESHOOTING GUIDE

SYMPTOMS
Motor does not start
or shuts down
Overheating
No power present
Machine noisy
Circuit breaker is
tripped
MAINTENANCE REPAIRS
If maintenance or repairs are required, contact one of our approved agents. For
quick and effective service, your agent will need to know the model, type and code
numbers of your generator set.
118030-Manual-C.indd 33
PROBABLE CAUSES
1- Generator set placed on load during
start-up.
2-Petrol or oil dipstick too low.*
3- Start-up control set to «OFF»
4- Fuel cock closed*
5- Fuel system blocked or leaky*
6- Air filter blocked
1- Ventilation opening blocked
2- Probable overload
1- Circuit breaker tripped
2- Defective circuit breaker
3- Defective female connector.
4- Defective equipment power cable
5- Defective AC generator.
1- Ball bearing broken
1- Defective exhaust
1- Generator set overload
2- Defective equipment or cable
CORRECTIVE ACTIONS
1- Remove load
2- Fill with petrol or oil
3- Set control to «ON»
4- Open cock
5- Return system to operational condition
6- Clean air filter
Clean intake and exhaust protectors
2- Check load
1- Switch on circuit breakers
2- Have checked, repaired or replaced
3- Have checked, repaired or replaced
4- Replace cable
5- Have checked, repaired or replaced
1- Inspect and replace
2- Inspect and replace
1- Reduce load
2- Have checked, repaired or replaced
EN
6/09/11 10:55:10