THERMOSTAT ASSEMBLY (AZCE6BLUEFACEC / AZCE6THINKR / AZCE6LITER)

Airzone thermostats are mounted on the wall through a support. It is recommended not to locate it more than 40 meters away
from the main control board. To fix it to the wall, follow these steps:
Separate the back part of the thermostat from the wall support and make all the
connections (AZCE6BLUEFACEC) or insert the CR2450 button battery
(AZCE6THINKR and AZCE6LITER).
Fix the back part of the thermostat to the wall.
Place the display on the support once it is fixed.
Place the anti-theft rods for additional support (optional).

INDOOR UNIT CONNECTION

Disconnect the power supply of the Daikin indoor unit and the Airzone system.
Find the P1, P2 connection of the Daikin indoor unit (where the thermostat is connected).
Connect the Airzone Gateway to the P1 P2 port of the Daikin unit using the twisted shielded cable supplied by Airzone. Do
not forget to respect the polarity.
Remember: Do not place the system bus close to lines of force, fluorescent lights, motors, etc. It might cause interference on
communications.
Configure the microswitchs as required (see Microswitch table).
Power the Daikin indoor unit and the Airzone system. Check the gateway LEDs (self-diagnosis).
Note: Disable the Stand by function using the Daikin controllers for a proper operation of the Airzone system.
Service Settings > Field Settings > 1e-2-01.
If you have any doubt, please check the Instruction manual Daikin BRC1E52A7.
SW1
Set point
SW1
P1 – Red
P2 - Black
ES
EN
FR
IT
PT
DE
Algorithm
ON*
OFF
-2
+4
Defrost
OFF*
ON