5° OPEN - Leaf 2 decelerates at closing (it stops
automatically on reaching the stop limit)
6° OPEN - Leaf 1 closing movement begins
7° OPEN - Leaf 1 Decelerates at closing (it stops
automatically on reaching the stop limit)
The DL10 LED stops flashing and the gate is ready for normal
operation.
Notes:
•The deceleration pulse should be supplied a little
earlier with respect to the stop limit to prevent the leaf
reaching it at full speed (it would be taken for an
obstacle).
•If only one leaf is present, the entire sequence must
nevertheless be effected. When the leaf has finished
opening, supply 5 Open pulses until the leaf begins to
close, and then resume normal operation.
6.3.4. LEARNING TIMES WITH ENCODER + LIMIT-SWITCHES
Learning with the encoder + Limit-switches can be done in two
different ways:
- SIMPLE LEARNING:
Carry out the same procedure as for limit-switch learning. The
encoder is used only as an obstacle sensor.
- COMPLETE LEARNING:
Carry out the same procedure as for limit-switch learning. The
encoder is used only as an obstacle sensor.
Note:
•If some limit-switches are not installed, start the
corresponding deceleration by supplying an Open
pulse (which replaces the limit-switch).
•If only one leaf is present, the entire sequence must
nevertheless be effected. When the leaf has finished
opening, supply 5 Open pulses until the leaf begins to
close, and then resume normal operation.
6.4.
PRE-FLASHING
If you wish to increase the equipment's safety level, you can
activate the pre-flashing function which enables the flashing
lamp to go on 5 seconds before the leaf starts to move.
Pre-flashing activation procedure:
1 - check if the gate is closed
2 - open and keep open the Stop contact
3 - check if the DL10 LED is OFF (if lighted, pre-flashing is
already active)
4 - briefly press the F push-button and check if the DL10 LED
lights up.
5 - close the Stop contact (DL10 goes OFF).
Procedure for disabling the function:
1 - check if the gate is closed
2 - open and keep open the Stop contact
3 - check if the DL10 LED is lighted (if OFF, pre-flashing is
already disabled)
4 - briefly press the F push-button and check if the DL10 LED
is OFF.
5 - close the Stop contact

7. AUTOMATED SYSTEM TEST

When you have finished programming, check if the system is
operating correctly.
Most important of all, check if the force is adequately adjusted
and if the safety devices are operating correctly.