Display control
To view a list access Main menu > Events and select the type of event to view. The alarms, notifications and string
warnings viewed are events in real time. The reasons for stopping are displayed as a history. To see more details
about a stop reason, once the list is complete, select it via
2016-01-11
2016-01-11
17:04 11-17 Low PV power
17:04 11-17 Low PV power
You can see a maximum of 25 reasons for shutdown, so once this number is reached, the unit deletes the oldest as
it needs space to store new entries. Furthermore, from this menu, you can delete the stop reason history.
10.20. See inverter data
To see the inverter serial number, the firmware versions installed or the configured country / regulation access Main
menu > Inverter data.
N/S
Inverter serial number.
FW APP
Firmware application
FW BOOT
Firmware start-up.
Pressing
and
allows navigating through a series of screens that display different inverter data.
10.21. Reset to default settings
If you want to delete all configurations made and accumulated values, thus returning the unit to the default
settings, you need to perform a reset.
To perform a factory reset access Main menu > Advanced settings > Factory reset. Press
10.22. Perform a ventilation test
Occasionally you need to test the proper performance of the unit's fans. These units have the option of performing
a ventilation test.
To perform the ventilation test access Main menu > Settings > Test Fans. Press
fans start to turn. Wait until the display shows that the test has finished. If one or several of the fans do not turn, a
ventilation fault is displayed. If all ventilators turn, the test's result is positive.
The ventilation test only checks the turning of the fans. A positive ventilation test alone does
not indicate that the system's ventilation status is correct. To assure proper performance of the
ventilation system, also check that there are no elements obstructing air passage and that the fans
are properly installed.
10.23. Performing an autotest
Autotest allows for the grid voltage and frequency limits to be tested automatically, checking that the unit
disconnects correctly within the time set by standard. This menu is only available for standards CEI 0-21 SPI
INTERNO, CEI 0-16 and DEWA INTEGRATED IPS.