Configuration
To reduce the chance of tripping this breaker, all Inverter/Chargers are pre-set to automatically limit the input current as described in "Most
Limiting" below. If your unit is equipped with DIP switches 7 and 8, they may be used to select other AC input current sharing settings.
Verify that AC input wiring is rated for the higher current that results when using the other settings.
Select Battery Charger-Limiting Points
"Most Limiting" (#7 & #8 Up): Charger-
limiting takes effect the moment any AC load
is applied; charger output falls gradually from
full output at no AC load passing through to
no output at full load (factory setting).
"Less Limiting" (#7 Up & #8 Down):
Charger-limiting begins when the Inverter/
Charger's load reaches 33% of the Inverter/
Charger's load rating. Charger output falls
gradually from full output at 33% of the
Inverter/Charger's load rating to about 33% of full output at full load.
230V Operation (APSX3024SW)
9 10
Select Low VAC Input Voltage Point for Switching
to Battery - OPTIONAL*
Voltage
9, 10 Switch Position
180 VAC
Up, Up
170 VAC
Up, Down
160 VAC
Down, Up
150 VAC
Down, Down (factory setting)
208V Operation (APSX6048VRNET model with Switch #4 in "Up" position)
9 10
Select Low VAC Input Voltage Point for Switching
to Battery - OPTIONAL*
Voltage
9, 10 Switch Position
175 VAC
Up, Up
165 VAC
Up, Down
175 VAC
Down, Up
165 VAC
Down, Down (factory setting)
230V Operation (APSX6048VRNET model with Switch #4 in "Down" position)
9 10
Select Low VAC Input Voltage Point for Switching
to Battery
Voltage
9, 10 Switch Position
180 VAC
Up, Up
170 VAC
Up, Down
180 VAC
Down, Up
170 VAC
Down, Down (factory setting)
* Most of your connected appliances and equipment will perform adequately when your Inverter/Charger's High AC Input Voltage Point and its Low AC
Voltage Input Point is left in the factory setting. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that
would have little effect on equipment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low
AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.
"Least Limiting" (#7 Down & #8 Up):
Charger-limiting begins when the Inverter/
Charger's load reaches 66% of the Inverter/
Charger's load rating. Charger output falls
5
6
7
8
5
6
7
8
5
6
7
8
gradually from full output at 66% of the
5
6
7
8
Inverter/Charger's load rating to about 66% of full output at full load.
"No Limiting" (#7 & #8 Down): No charger-
limiting occurs at any load size.
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
11
Select High AC Input Voltage Point for Switching to
Battery - OPTIONAL*
Voltage
270 VAC
260 VAC
11
Select High AC Input Voltage Point for Switching to
Battery - OPTIONAL*
Voltage
245 VAC
235 VAC
11
Select High AC Input Voltage Point for Switching to
Battery - OPTIONAL*
Voltage
270 VAC
260 VAC
6
Switch Position
Up
Down (factory setting)
Switch Position
Up
Down (factory setting)
Switch Position
Up
Down (factory setting)
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8
5
6
7
8