4
Installation
4.4 Electrical Connection
All electrical work should be carried out by a suitably qualified technician. Failure
to comply with this could lead to electrocution, fire, and death. It will also invali-
date product warranty. All wiring should be according to national wiring regula-
tions.
Breaker abbreviation
Meaning
ECB1
Earth leakage circuit breaker for booster heater
ECB2
Earth leakage circuit breaker for immersion heater
TB1
Terminal block 1
ECB1 ECB2
A
E
B
F
C
D
TB1
<1 phase (with immersion heater)>
Cylinder unit powered via outdoor unit
(If you want to use independent source, go to the Mitsubishi website.)
<1 phase>
Affix label A that is included with the manuals near each
wiring diagram for cylinder unit and outdoor units.
Power supply
~/N 230 V 50 Hz
Description
Booster heater (Primary circuit)
Immersion heater (DHW tank)
Cylinder unit - Outdoor unit
Cylinder unit - Outdoor unit earth
Cylinder unit - Outdoor unit S1 - S2
Cylinder unit - Outdoor unit S2 - S3
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. Insufficient power supply capacity might cause chattering.
ECB1
A
E
B
C
D
TB1
<3 phase (without immersion heater)>
Outdoor unit
Wiring cir-
Earth
leakage
cuit breaker
L
or
circuit
breaker
Isolating
N
*1 ,*2
switch
Power supply
~/N 230 V 50 Hz
Power supply
~/N 230 V 50 Hz
<Figure 4.4.1>
Electrical connections 1 phase
Power supply
Capacity
~/N 230 V 50 Hz
2 kW
6 kW
~/N 230 V 50 Hz
3 kW
*3
3 × 1.5 (polar)
*3
1 × Min. 1.5
*4
230 V AC
*4
The cylinder unit can be powered in two ways.
1. Power cable is run from the outdoor unit to the cylinder unit.
2. Cylinder unit has independent power source
Connections should be made to the terminals indicated in the figures to the left
below depending on the phase.
Booster heater and immersion heater should be connected independently from
one another to dedicated power supplies.
Locally supplied wiring should be inserted through the inlets situated on the
top of the cylinder unit. (Refer to <Table 3.4>.)
Wiring should be fed down the right hand side of the control and electrical
box and clamped in place using clips provided.
The wires should be inserted individually through the cable inlets as below.
2 Outputs wire
3 Indoor-Outdoor wire
5 Power line(B.H.)/ Power line(I.H.)(Option)
7 Signal input wires
Connect the outdoor unit – cylinder unit connecting cable to TB1.
Connect the power cable for the booster heater to ECB1.
If immersion heater is present, connect the power cable to ECB2.
• Avoid contact between wiring and parts (
• Make sure that ECB1 and ECB2 are ON.
• On completion of wiring ensure main remote controller cable is con-
nected to the relay connector.
Cylinder unit
TB1
L
N
To control
board
S1
S1
S2
S2
S3
S3
ECB1
Wiring
For
circuit
L
booster
breaker or
heater
Isolating
N
(Primary circuit)
switch
ECB2
Wiring
circuit
For
L
breaker or
immersion
Isolating
heater
N
switch
(DHW tank)
Breaker
Wiring
16 A *2
2.5 mm²
32 A *2
6.0 mm²
16 A *2
2.5 mm²
24 V DC
8
7
4
1
2
3
).
*1. If the installed earth leakage circuit breaker
does not have an over-current protection
function, install a breaker with that function
along the same power line.
*2. A breaker with at least 3.0 mm contact separa-
tion in each pole shall be provided.
Use earth leakage breaker (NV).
The breaker shall be provided to ensure
disconnection of all active phase conductors
of the supply.
*3. Max. 45 m
If 2.5 mm² used, Max. 50 m
If 2.5 mm² used and S3 separated, Max. 80 m
*4. The values given in the table above are not
always measured against the ground value.
5
6
en
14