POWERVAR
- SECURITY ONE UNINTERRUPTIBLE POWER MANAGER
Operating Voltage: The DIP switches can be used to configure the UPM operating voltage. For North
American models, the UPM can be configured to operate at 100, 110, 115, or 120 volts. International
models can be configured for 220, 230, or 240 volts. The following table illustrates the required switch
settings for each selection. (Not available in Rackmount Version)
Voltage Required
100V/208V
110V/220V
120/230V
127/240V
If Communications Manager software is installed on the host PC, Configuration Manager can use it to adjust
both Low Voltage Transfer Point and High Voltage Transfer Point. The following table provides the
allowable set points for adjusting transfer voltage (key in all three numbers shown).
Low Voltage Transfer Points (key in all three numbers)
Model
North American
International
High Voltage Transfer Points (key in all three numbers)
Model
North American
International
Low Battery Warning Time: Low battery warning time can be configured for either two or five minutes
before UPM shutdown depending on the requirements of the application. It should be noted that these times
are at full load with a healthy battery. Partial loads and/or aged batteries will affect the accuracy of this timer
setting.
Receptacle On/Off Control: Set the turn-off times of the receptacle groups and individual receptacles on
the rear panel.
SW#1
SW #2
SW #3
On
Off
Off
Off
On
Off
Off
Off
On
Off
Off
Off
Set Pt.
Set Pt.
Set Pt.
Set Pt.
1
2
3
089
091
093
176
181
186
Set Pt.
Set Pt.
Set Pt.
Set Pt.
1
2
3
141
145
148
282
290
296
13
SW #4
Off
Off
Off
On
4
096
192
4
151
302