Scope of delivery and options

3.1

Scope of delivery

The Scope of delivery includes:
• cooling unit (with connection for door contact switch)
Enclosed package (among other things sealing profile, faste-
ning material, electrical plug-type connectors)
special accessories, if applicable.
3.2
Options
Options on request or in accordance with the catalogue.
4

General Information

Old devices can be properly disposed of by Pfannenberg.
They must be sent to one of our works shipment/postage paid.
All cooling units produced by Pfannenberg are free from
siliconecompounds,
PCB,
PCT,
asbestos,
formaldehyde,
cadmium,
substances impairing wetting.
Every cooling unit is checked to ensure that it is tight according
to the provisions of UVV-BGV D4 (German regulations covering
accident prevention).
Prior to delivery the electrical safety of every cooling unit is
factory tested. This means that, in accordance with UVV-BGV
A2, §5 (4), the operating company is released from the obliga-
tion to arrange for a test of the electrical part of the cooling unit
before initial start of operation.
5

ID Plate and Technical Data

For installation and maintenance, note the data on the ID plate; it is
to be found on the back of the cooling unit casing
The technical details applicable to the cooling unit are in the
supplement.
frequency
nominal voltage
unit type
part number
serial number
nominal current
starting
current
exterior/interior
conditions
electrical
refrigerant
energy
085 408 065f
6
Cooling units produced by Pfannenberg are designed for
dissipating heat from switch cabinets (IP 54). During each cooling
process condensate can be produced. The cooling unit is only
suitable for stationary operation.
The cooling unit may only be used under the ambient conditions
specified on the enclosed sheet.
The cooling unit is to a large measure maintenance-free (see Section 11).
Every other use is considered as non-authorized use making any
warranty null and void.
The electrical equipment must be regularly checked. Any faults
such as loose connections or scorched cables must be removed
immediately.
Work on the cooling system and on electrical components may only
be carried out by authorized specialist personnel.
Compliance with applicable safety and environmental regulations
is mandatory.
Only original spare parts may be used.
7
7.1
1
2
3
4
5
6
7
The compressor (1) compresses the refrigerant until high pressure
is achieved. During this process temperature increases. In the
condenser (2) heat is dissipated to ambient air, the coolant becoming
type of fuse
liquid. The condenser fan (5) of the condensator takes ambient air
in through the condenser, then it releases the air.
The pressure of the coolant drops as it passes through the ex-
pansion device (3). In the evaporator (4) the coolant absorbs
heat from the air in the switch cabinet and evaporates. Thus, the
air in the switch cabinet cools down. At the same time the air
inside the switch cabinet is being dehumidified. The evaporator
fuse
fan (6) sucks the air out of the switch cabinet via the evapora-
tor, the cooled air flows back to the switch cabinet.
The cooling unit is electronically controlled. For that purpose a
temperature sensor records the temperature of the air inside the
switch cabinet (7).
The refrigerant is not detrimental to the ozonosphere; it is hardly
combustible.
7.2
During cooling on the evaporator the moisture removed from the air
is collected as condensate. In order to avoid any damage to the
pressure of
cooling
switch cabinet and the cooling unit, the condensate must be
capacity
refrigerant
discharged.
The condensate is discharged in the following way:
Always ensure that the condensate is drained properly (safety-
drainage).
Excessive condensation can occur if, for example, the switch
cabinet is not sealed or if the internal temperature of the switch
cabinet is frequently below the dew point.

Safety

Hazard!
Isolate the cooling unit from the mains before carrying out
any cleaning or maintenance operations.

Function

Principles of function

Compressor
Heat exchanger
(condenser)
Expansion device
Heat exchanger
(evaporator)
fan, exterior circulation
fan, inner circulation
Electronic control system with temperature sensor

Condensate

In case of normal condensate drainage a reservoir collects the