Table of confi guration parameters

10.1 1st level parameters

1
Sensor
Sen.
Select type of sensor.
Thermocouple type K. Range: -260..1360°C > Default
tc. k
Thermocouple type S. Range: -40...1760°C
tc. S
Thermocouple type R. Range: -40...1760°C
tc. r
Thermocouple type J. Range: -200...1200°C
tc. J
Thermocouple type T. Range: -260...400°C
tc. t
Thermocouple type E. Range: -260...1000°C
tc. E
Thermocouple type N. Range: -260...1280°C
tc. n
2
Offset Calibration
o.caL.
Number added to visualized process (normally it corrects ambient
temperature value).
-99.9...+99.9 tenths of degree. Default: 0.0.
3
Gain Calibration
G.caL.
Number multiplied with process value to calibrate working point.
-99.9%...+99.9%. Default: 0.0.
4
Upper Limit Setpoint
up.L.s.
Setpoint upper limit.
0...+3200 degrees. Default: 1250.
5
Degree
dEGr.
Select type of degree.
Centigrade. > Default.
Fahrenheit.
6
Tune
Tune
Select autotunig type.
Disabled. > Default.
Dis.
Automatic. Controller checks constantly the process value and
Auto.
modifies P.I.D. values (if necessary).
Manual. Started by keys.
Man.
7
Setpoint Deviation Tune
s.d.tu.
Selects deviation from command setpoint as threshold used by manual
tuning to calculate P.I.D. parameters.
0.0...500.0 tenths of degree. > Default: 5.0.