Hold Function - Pixsys ATR 902 Manual Instalador

Ocultar thumbs Ver también para ATR 902:
Idiomas disponibles
  • ES

Idiomas disponibles

16
Special Functions
sp.fu.
Enables simple thermoregulator function and manual setting of output
percentage.
(Disabled) No function available. > Default.
dis.
(Thermoregulator) Enables simple thermoregulator function.
tHer.
(Manual) Enables manual mode.
man.
(Thermoregulator and Manual) Enables both simple thermoregula-
tH.ma.
tor and manual function.
17

Hold Function

HLd.F.
Enables
"Hold"
keyboard.
(Disabled)
dis.
(Enabled)
En.
18
Cycles Available
cy.au.
Selects number of available cycles.
1...15 cycles. > Default: 15.
19
Block Programming Cycles
b.pr.c.
Selects number of cycles that the user cannot modify (these can be pre-
programmed by the manufacturer/installer to avoid wrong progamming).
Ex.: selecting 3 the programming of the first 3 cycles is locked.
0...15 locked cycles. > Default: 0.
20
Waiting Time Step End
w.t.s.e.
Selects time for step end waiting in hh.mm.
00.00 Step end waiting excluded
00.01...24.00 hh.mm. > Default: 01.00.
21
Max. Gap Step End
m.G.s.e.
Selects max. gap for step end waiting activation. When the difference
between setpoint and process is lower than this parameter, the controller
switches to the next step (also without waiting for the time programmed on
parameter 36 w.t.s.e )
0...200 degrees. > Default: 5.
22
Recovery Interrupted Cycle
r. i .cY.
Enables the interrupted cycle recovery function.
0 Cycle recovery disabled
1 Cycle recovery enabled with automatic gradient. > Default.
2...1000 degrees/hour. Select recovery gradient.
22 - ATR902 - User manual
function; allows to hold the cycle and modify setpoint by
function disabled. > Default.
"Hold"
function enabled.
"Hold"
loading