11.e
Auxiliary output related to the step
Step 4
Step 3
Step 2
Step 1
OUT
ON
OFF
12
Table of Anomaly Signals
If installation malfunctions, controller switches off regulation output and reports
the anomaly.
For example, controller will report failure of a connected thermocouple visualizing
E-05 (flashing) on display. For other signals see table below:
E-0 1
Error in EEPROM cell programming.Call Assistance.
sYs.e.
E-03
Incorrect cycle data.
eep.e.
Incorrect configuration data.
E-04
Possible loss of instrument
calibration.
sYs.e.
Sensor connected to AI1
E-05
broken or temperature out of
prb. 1
range.
E-08
Missing calibration.
sYs.e.
Cold junction sensor failure or
E- 1 1
room temperature outside of
allowed limits.
sYs.e.
28 - ATR902 - User manual
Step 5
Cycle end
Step 6
Operator stop
Time
Cause
ON/OFF status of the auxiliary output
is selectable for each step of each
cycle. The status can be selected also
at cycle end.
Riprogrammare il ciclo
Verify that configuration
parameters are correct.
Control connection with probes
and their integrity.
Call Assistance.
Call Assistance.
How to do