6. 6. Chimney
Chimney
Previas_Kwikco_10_(c-f-i)040511
The steam outlet chimney should be installed by authorized
professionals according to local regulations.
The dimensions for connection to the chimney are shown in
the following table:
KX-4/5+H
KL-4/5+H
KX-9/10+H
KL-9/10+H
Fundamental aspects:
•
The chimney should preferable be insulated along its
length and not in contact with combustible materials
(such as wooden beams or ceilings).
•
Sections should not be horizontal, but should instead
have a slope of at least 10º without bends or elbows
of radius less than twice the tube diameter.
•
The chimney should incorporate a system for preven-
ting backflow of condensates.
•
It is recommended that the chimney used be insulated
and of interior diameter 2 1/2" .
•
The steam outlet pipe from the oven should be cou-
pled to this chimney.