Parameter [C]
Indoor unit
capacity
07
09
12
15
type
Refrigerant
0.06
0.03
0.14
0.29
amount
(0.03)
(0.014)
(0.06)
(0.13)
(lbs. (kg)/unit)
Indoor unit
FXFQ type
capacity
07
09
12
15
type
Refrigerant
0.36
0.33
0.30
0.26
amount
(0.16)
(0.15)
(0.14)
(0.12)
(lbs. (kg)/unit)
Example for refrigerant branch using REFNET joint and REFNET
header for systems and each pipe length is shown below. (Example
7.5. System piping (length) limitations on page 11.)
Outdoor system: RXYQ240TAYCU (RXYQ120TAYCU+RXYQ120TAYCU)
Indoor units
FXMQ type: 18 × 1, 24 × 1, 30 × 1, 36 × 2
FXFQ type: 36 × 2
Other: 48 × 1
Liquid piping
a: f3/4 × 60 ft.
e: f1/4 × 15 ft.
i: f3/8 × 20 ft. m: f3/8 × 15 ft. r: f1/2 × 10 ft.
b: f5/8 × 20 ft.
f: f3/8 × 10 ft.
j: f3/8 × 10 ft. n: f3/8 × 15 ft.
c: f1/2 × 10 ft.
g: f3/8 × 10 ft. k: f3/8 × 10 ft. o: f3/8 × 10 ft.
d: f3/8 × 15 ft.
h: f3/8 × 15 ft.
: f3/8 × 15 ft. p: f3/8 × 10 ft.
Total length of liquid piping: 285 ft.
Total capacity of indoor unit: 110.0%
[C] = 0.25×1 + 0.16×1 + 0.33×1 + 0.25×2 + 0.53×2 + 0.00×1 = 2.30 lbs.
↑
↑
↑
FXMQ18x1
FXMQ24x1
FXMQ30x1
[B]: The smaller of [C] or 6.61 lbs. = 2.30 lbs.
R = ( 60×0.175 + 20×0.121 + 35×0.081 + 155×0.040 + 15×0.015 ) + 19.4 + 2.30
↑
↑
↑
a
b
c, r, t
d, f, g, h, i,
j, k, , m,
= 43.88 ⇒ 43.9 lbs.
Round off in units of 0.1 lbs.
INFORMATION
Piping length is considered by the distance from the outdoor unit to the
farthest indoor unit.
27
FXMQ type
18
24
30
36
48
54
0.25
0.16
0.33
0.25
0.08
0.00
(0.11)
(0.07)
(0.15)
(0.11)
(0.04)
(0.00)
Others
18
24
30
36
48
0.61
0.53
0.61
0.53
0.36
0.00
(0.28)
(0.24)
(0.28)
(0.24)
(0.16)
(0.00)
t: f1/2 × 15 ft.
↑
↑
↑
FXMQ36x2
FXFQ36x2
Other48x1
↑
↑
↑
↑