Measurement Specifications - Ideal SureTest 61-164 Manual De Instrucciones

Analizador de circuitos
Ocultar thumbs Ver también para SureTest 61-164:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ND 5481-6 61-164 165 Ins
8/28/08
General Specifications
Characteristics
Display
Display update for Volt
Over-range Indication on all functions
Operating Environment,
Relative Humidity
Storage Environment:
Case Construction:
Altitude:
Dimensions:
Weight:
Safety:
Accessories:
Double Insulation
Instrument has been evaluated and complies with insulation category III (overvoltage cate-
gory III). Pollution degree 2 in accordance with IEC-644. Indoor use.
1:55 PM
Page 13
Description
128 x 64 OLED with backlight
Less than 2.5 times Second.
Display "OL"
32°F to 122°F (0°C to 50°C) at <80%RH
32°F to 122°F (0°C to 50°C) at <80% RH
ABS UL 94V/0/5VA rated
6561.7 ft (2000m)
6.4" (L) x 3" (W) x 1.4" (D)
162mm (L) x 76mm (W) x 36mm (D)
9.4 oz (267g)
UL61010B-1, Cat III-300V
UL-1436 for AFCI, GFCI & Outlet
C
US
Includes 1' plug adapter, carrying case,
instruction manual. Optional alligator clip
adapter available.
13

Measurement Specifications:

All specifications are at 23°C ± 5°C at less than 80% relative humidity.
Accuracy is state as ± ([% of range] + [counts]).
AC converter is true rms sensing.
Measurement
Ranges
Line Voltage
85.0 - 250.0 VAC
Peak Line Voltage
121.0 - 354.0 VAC
Frequency
45.0 - 65.0 Hz
% Voltage Drop
0.1% - 99.9%
Voltage Loaded
10.0 - 250.0 VAC
Neutral-Ground V
0.0 - 10.0 VAC
Impedance - Hot
0.00 Ω - 3.00 Ω
Neutral, & Ground
> 3 Ω
GFCI Trip Time
1mS to 6.500S counter.
GFCI Trip Current
6.0 - 9.0 mA
EPD Trip Current
30.0 - 37.0 mA
Resolution
Accuracy
0.1V
1.0% ± .2V
0.1V
1.0% ± .2V
0.1Hz
1.0% ± .2Hz
0.1%
2.5% ± .2%
0.1V
2.5% ± .2V
0.1V
2.5% ± .2V
0.01Ω
2.5% ± .02Ω
Unspecified.
1 mS
1.0% ± 2mS
0.1 mA
1.0% ± .2mA
0.1 mA
1.0% ± .2mA
14
Tabla de contenido
loading

Este manual también es adecuado para:

Suretest 61-165

Tabla de contenido