Ideal SureTest 61-164 Manual De Instrucciones página 3

Analizador de circuitos
Ocultar thumbs Ver también para SureTest 61-164:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ND 5481-6 61-164 165 Ins
8/28/08
Troubleshooting Tips for Voltage Issues
Measurement
Expected
Problem
Result
Line Voltage
120VAC
108-132VAC
High/low
220VAC
198-242VAC
Neutral-Ground
<2VAC
High G-N
Voltage
Voltage
>2VAC
Peak Voltage
120VAC
153-185VAC
High/low
220VAC
280-342VAC
peak voltage
High/low
Frequency
60HZ
frequency
WARNING: Do not exceed the unit's maximum voltage rating of 250VAC.
Voltage Drop (V
) Measurements
D
The SureTest measures the line voltage, applies a load on the circuit, measures the loaded
voltage, then calculates the voltage drop. Results are displayed for 12A, 15A, and 20A
loads. The National Electrical Code recommends 5% as the maximum voltage drop for
branch circuits for reasonable efficiency (NEC article 210-19. FPN 4). And, the voltage
under load (V
) should not drop below 108VAC for reliable equipment operation.
L
A good branch circuit should start out with less than 5% voltage drop at the furthest recep-
tacle from the panel at the end of the cable run. Then, each receptacle tested in sequence
towards the panel should show a steady decrease in voltage drop. If the voltage drop is
above 5% and does not noticeably decrease as you get closer to the first device on the cir-
cuit, then the problem is between the first device and the panel. Visually check the termina-
tions at the first device, the wiring between the device and the panel, and the circuit breaker
1:55 PM
Page 5
Possible
Possible
Causes
Solutions
Too much load on
Redistribute loads
the load on circuit.
on the circuit.
High resistance
Locate high resistance
connection within
connection/device and
the circuit or at
repair/replace.
the panel.
Supply voltage
Consult power
too high/low.
company.
Current leaking
Identify source of leakage:
from neutral to
multiple bonding points,
ground.
equipment or devices.
Unbalanced 3-
Check load balance
phase system.
and redistribute load.
Triplen harmonics
Oversize neutral to
returning on
impedance. Reduce
neutral in 3-phase
harmonic effect via
system.
filter or other methods.
Supply voltage
Consult power
too high/low.
company.
High Peak Loads
Evaluate number of
on line caused by
electronic devices on
electronic equipment
circuit and redistribute
on line.
if necessary.
Supply frequency
Consult power
too high/low.
company.
5
connections. High resistance points can usually be identified as hot spots using an infrared
thermometer or by measuring the voltage across the breaker. If the voltage drop exceeds
5% but noticeably decreases as you nearer the panel, the circuit may have undersized wire,
too long of a cable run, or too much current on the circuit. Check the wire to ensure that it
is sized per code and measure the current on the branch circuit. If a voltage drop reading
changes significantly from one receptacle to the next, then the problem is a high impedance
point at or between two receptacles. It is usually located at a termination point, such as a
bad splice or loose wire connection, but it might also be a bad receptacle.
Troubleshooting Tips for Voltage Drop
Measurement
Expected
Problem
Result
High Voltage
Voltage Drop
<5%
Drop
Estimated Load on Line (ELL) Measurement
The SureTest now estimates the load on a branch circuit to provide an indication of how
much capacity in the circuit remains or to quickly check if the circuit is dedicated. This
function is a rough estimate (no stated accuracy), as accurately measuring circuit current
has to be done with a clamp meter at the electrical panel. The proprietary way in which
these calculations are made allows the user to plug the unit into an outlet and quickly deter-
mine the current load on that branch circuit.
Both the distance of the SureTest from the load and branch circuit impedance will affect
accuracy. Best accuracy is obtained by positioning the SureTest in the same outlet as the
largest load on line; otherwise, try to position the SureTest between the load(s) and the
electrical panel. The maximum amperage reported by the tester is 15A.
ASCC Measurement
The SureTest calculates the Available Short-Circuit Current (ASCC) that the branch circuit
can deliver through the breaker during a bolted fault (dead-short) condition.
The ASCC is calculated by dividing the line voltage by the circuit's line impedance (hot +
neutral). Depressing the side arrow (
) displays the worst-case scenario where all three
conductors (hot, neutral, ground) are shorted together -- the neutral and ground provide a
lower impedance via a parallel return path. Note that this second test will trip a GFCI. See
the following equations for clarification.
Possible
Possible
Causes
Solutions
Too much
Redistribute the
load on
load on
the circuit.
the circuit.
Undersized wire for
Check code requirements
length of run.
and re-wire if necessary.
High resistance
Locate high
connection within
resistance connection/
the circuit or at
device and
the panel.
repair/replace.
6
Tabla de contenido
loading

Este manual también es adecuado para:

Suretest 61-165

Tabla de contenido