Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Power supply
teminal block (2P)
Transmission
Control box
terminal block (6P)
Ground terminal
Clamp (4)
Insulating tube (11)
Control box
Control box lid
lid secuing screw (2pcs.)
L
L
1
2
POWER SUPPLY
power supply
How to connect power supply
terminal block (2P)
Clamp (4)
Fastener
Power supply wire
Clamp (4)
Fastener
Fig. 27
Transmission
P 1 P 2 F 1 F 2 T 1 T 2
terminal block (6P)
REMOTE
TRANSMISSION
CNTRL
1 in.
Transmission wire
In the insulating tube (11), it can let the remote controller wire
and transmission wire pass to 2.
WARNING
Never connect power supply wiring to the terminal block for
remote controller wiring as this could damage the entire system.
Use only specifi ed wire and connect wires to the terminal
tightly. Be careful wires do not place external stress on ter-
minals. Keep wires in neat order so as to not obstruct other
equipment. Make sure that the electric box lid fi ts tightly.
Incomplete connections could result in overheating and, in
worse case, result in electric shock or fi re.
NOTE
1. Use round crimp-style terminals for connecting wires to the
power supply terminal block.
If unavailable, observe the following points when wiring.
Do not connect wires of different gauge to the same
power supply terminal.
(Looseness in the connection may cause overheating.)
English
Refer to Fig. 27
Remote controller wire
and transmission wire
Power supply wire
Gas pipe
Liquid pipe
Drain pipe
Conduit
Corking or Putty
Resin bush (10)
Fig. 26
Ground wire
After securing the
cramp material
to the bracket,
cut off any extra
material.
Remote controller wire and
transmission wire
FORCED
WIRING
OFF
Clamp (4)
Insulating
tube (11)
Remote controller wire
Fig. 28
Use the specifi ed electric wire. Connect the wire securely to
the terminal. Lock the wire down without applying excessive
force to the terminal. (Tightening torque: 0.97 ft lbf ±10%)
Attach insulation sleeve
Round crimp-style terminal
Connect wires of the
same gauge to both side.
2. Tightening torque for the terminal screws.
Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not be
properly tightened.
If the terminal screws are tightened too hard, screws
might be damaged.
Refer to the table below for the tightening torque of the
terminal screws.
Table 4
Terminal
Transmission terminal block (6P)
Power supply terminal block (2P)
Ground terminal
3. Do not connect wires of different gauge to the same ground
terminal. Looseness in the connection may deteriorate pro-
tection.
4. Outside of the unit, keep transmission wire at least 5 in.
away from power supply wire. The equipment may malfunc-
tion if subjected to electrical (external) noise.
5. For remote controller wire, refer to the "INSTALLATION
MANUAL OF REMOTE CONTROLLER" attached to the
remote controller.
9-2

WIRING EXAMPLE

Fit the power supply wire of each unit with a switch and fuse
as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
Power supply
Outdoor unit
Main
switch
Indoor unit
Remote controller
Electric wire
Tightening torque
Size
(ft-lbf)
M3.5
0.58 – 0.72
M4
0.87 – 1.06
M4
0.87 – 1.06
Power supply wire
Transmission wire
Switch
Fuse
11
Tabla de contenido
loading

Este manual también es adecuado para:

Fhq24pvjuFhq30pvju

Tabla de contenido