7 MAINTENANCE
Gabarrón electric boilers do not need any special maintenance, only the following should be checked:
-Check the pressure indicated by the pressure gauge frequently, ensuring that it is between 1 and 1.5 bar when cold.
- Never start the boiler when it is empty.
- Never start the boiler when the S.H.W. tank is empty; to fill it for the first time open a hot water tap and wait until
water comes out of it.
-Precaution against freezing. In dwellings that are frequently unoccupied or at risk of freezing, an anti-freeze of the
appropriate quality can be added to the water of the heating installation – the concentration must not exceed 30%
in volume.
- Clean the surfaces of the boiler with a damp cloth, having previously disconnected it from the mains. Do not use
solvents or abrasive products.
8 TROUBLESHOOTING
Problem
Boiler will not start
Error E1
Error E2
Error E3
Lack of heating water flow.
Error E4
Error E5
Error E6
Heating safety valve expels water
S.H.W. safety valve expels water.
The buttons do not respond
Low temperature in the installation.
Possible cause
No current entering boiler.
Main switch is off.
Overheating of the heating.
Overheating of S.H.W.
S.H.W. tank empty.
Heating water out temperature
probe defective.
Heating water return temperature
probe defective.
Pump blocked.
Valves shut.
Air in the installation.
Pump blocked.
Valves shut.
Air in the installation.
Configuration error of the maximum
limited output.
S.H.W. temperature probe
defective.
Excessive pressure in cold.
Expansion vessel breakdown.
Water entering heating circuit.
Entering water pressure too high.
S.H.W. expansion vessel breakdown
Control panel blocked
Heating setting low.
Setting of ambient thermostat low.
Resistances broken down.
Badly calculated installation.
Solution
Check the installation.
Swith it on. See Section 6.1.
See Section 6.3.4.
See Section 6.4.2.
Open a hot water tap until the water
flows.
Contact Technical Service
Contact Technical Service
Unblock – see instructions
Open valves.
Purge the installation
Unblock – see Section 6.3.3.
Open valves.
Purge the installation.
See Section 5 LIMITATION OF
OUTPUT
Contact Technical Service
Adjust to between 1 & 1.5bar.
Change.
Check filling valve.
Install a pressure reducer.
Change.
See Section 10.2 BLOCKING THE
CONTROLS
Regulate.
Regulate.
Contact Technical Service.
Increase output.
27