TABLE "B" - LOGICS
Any modification of parameters/logics must be confirmed by pressing S2 > 5s
DIP
Logic
Transmitter
1
programming
2
BAR / 8K2
Photocell input
3
check
4
Edge input check
Photocells
5
during closing
Safety edge input
6
operation
7
Fast closing
Residential /
apartment
8
building
operation
Hammer during
9
opening
10
Not used
26 -
ALENA SW2 CPEM
INSTALLATION MANUAL
Cross out
Default
setting used
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
Description
Enables wireless memorizing of transmitters:
1- Press in sequence the hidden key and normal key (T1-T2-T3-T4) of a transmitter that has
already been memorized in standard mode via the radio menu.
2- Press within 10 sec. the hidden key and normal key (T1-T2-T3-T4) of a transmitter to be
memorized.
The receiver exits programming mode after 10 sec.: you can use this time to enter other new
transmitters.
This mode does not require access to the control panel.
IMPORTANT: Enables the automatic addition of new transmitters, clones and replays.
Disables wireless memorizing of transmitters and automatic addition of clones.
Transmitters are memorized only using the relevant Radio menu or automatically with re-
plays.
IMPORTANT: Disables the automatic addition of new transmitters and clones
Input configured as Bar 8k2 (Fig.G). Input for resistive edge 8K2.
The command reverses movement for 2 sec.
Input configured as Bar, safety edge (Fig.G).
The command reverses movement for 2 sec..
Enable safety check on the PHOT input. Fig.G
Safety check on PHOT input not enabled. Fig.G
Enable safety check on the BAR input. Fig.G
Safety check on BAR input not enabled. Fig.G
In the event beam is broken, photocell operation is disabled during opening. During closing,
movement is reversed immediately.
When beam is broken, photocells are active during both opening and clo-
sing. When beam is broken during closing, movement is reversed only once the
photocell is cleared.
Safety edge with active reversal only when closing, when opening the movement stops
Safety edge with active reversal in both directions
Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
Logic not enabled
Sets the automation type of operation:
ON = Apartment building
OFF = Residential
Reaction to the START input (wired or radio):
Residential
CLOSED
Opens
WHILE CLOSING
Stops
OPEN
Closes
WHILE OPENING
STOPS + TCA
AFTER STOP
Opens
Reaction to the OPEN input (wired):
Residential
CLOSED
Opens
WHILE CLOSING
Opens
OPEN
No effect
WHILE OPENING
Keeps it open
AFTER STOP
Opens
Reaction to the PEDESTRIAN input (radio):
Residential
CLOSED
Opens partially Opens partially
WHILE CLOSING
Stops
OPEN
Closes
WHILE OPENING
STOPS + TCA
AFTER STOP
Opens partially Opens partially
Before opening completely, the gate pushes for approx. 2 seconds as it closes. This allows
the solenoid lock to be released more easily.
IMPORTANT - Do not use this function if suitable mechanical stops are not in place.
Logic not enabled
Apartment
building
Opens
Opens
Closes
No effect
Opens
Apartment
building
Opens
Opens
No effect
Keeps it open
Opens
Apartment
building
Opens partially
Closes
No effect