1) GENERAL INFORMATION
The ALENA SW2 CPEM control panel comes with standard factory settings. Any
change must be set by means of the TRIMMER and DIP SWITCH settings.
Its main features are:
-
Control of 1 or 2 motors single-phase
Note: 2 motors of the same type must be used.
-
Electronic torque control
-
Slowdown while opening and closing
-
Separate inputs for safety devices
-
Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance
or replacement easier. It comes with a series of prewired jumpers to make the
installer's job on site easier.
The jumpers concern terminals: 70-71, 70-72, 70-74, 41-42, 41-43, 41-44,
41-45. If the above-mentioned terminals are being used, remove the rel-
evant jumpers.
TESTING
TheALENA SW2 CPEM panel controls (checks) the start relays and safety devices
(photocells) before performing each opening and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.
2) TECHNICAL SPECIFICATIONS
Power supply *
Low voltage/mains insulation
Terminal
L
N
GND
10
11
12
14
15
16
20
AUX 0 – 230V POWERED CONTACT
21
28
29
40
41
42
43
44
45
50
51
52
60
61
62
70
71
72
73
74
75
Y
#
(*) If "D" type devices are installed (as defined by EN12453), connect in unverified mode, foresee mandatory maintenance at least every six months.
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
INSTALLATION MANUAL
110-120V 60Hz
220-230V 50/60 Hz
> 2MOhm 500V
Definition
LINE
NEUTRAL
Single-phase power supply with earth cable
EARTH
START + CONDENSER
COM
Motor and condenser connection. Time lag during closing. (Can be adjusted with trimmer T4)
START + CONDENSER
START + CONDENSER
Motor and condenser connection. Time lag during opening. 2s
COM
Note: if T4=0, do not connect any cable to terminals 14-15-16
START + CONDENSER
Exit due to FLASHING LIGHT.
Contact stays closed while leaves are operating.
(N.O.) (40W MAX)
see Fig. F1-F2
Solenoid lock
Not used
+REF SWE
Limit switch common
SWC1
Motor 1 closing limit switch SWC1 (N.C.).
SWO1
Motor 1 opening limit switch SWO1 (N.C.).
SWC2
Motor 2 closing limit switch SWC2 (N.C.).
SWO2
Motor 2 opening limit switch SWO2 (N.C.).
~
0V
Accessories power supply output.
~
24V
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
~
24 Vsafe
Output active only during operating cycle.
Common
START and OPEN inputs common
START command button (N.O.).
START
Operation according to "3/4-STEP" logic
OPEN command button (N.O.).
OPEN
Gate opened with this command. If the input stays closed, the leaves stay open until the contact is opened.
When the contact is open, the automated device closes following the TCA time, where activated.
Common
STOP, PHOT and BAR inputs common
The command stops movement. (N.C.)
STOP
If not used, leave jumper inserted.
PHOTOCELL input (N.C.).
PHOT (*)
Operation according to "PHOTOCELL/PHOTOCELL DURING CLOSING" logic. If not used, leave jumper inserted.
FAULT 1
Test input for safety devices connected to PHOT.
Safety edge input (N.C.).
If not used, leave jumper inserted
BAR/8K2
dip
OFF
BAR /
OFF
BAR CL /
BAR TEST /
OFF
BAR CL TEST /
BAR 8K2 /
BAR CL 8K2
OFF
(*)
ON
ON
ON
ON
FAULT 2
Test input for safety devices connected to BAR.
Antenna input.
ANTENNA
Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver. Metal bodies
close to the antenna can interfere with radio reception. If the transmitter's range is limited, move the antenna
SHIELD
to a more suitable position.
Operating temperature range
Dielectric rigidity
Maximum motor power
Accessories power supply
Solenoid lock
AUX 0 - Flashing
Contact powered
Fuses
Built-in Rolling-Code
radio-receiver
Setting of parameters and logics
N° of combinations
Max.n° of transmitters that can be memorized 63
Pedestrian work time
Maximum work time
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
Description
Safety
Safety edge
edge
operation
check dip
dip
OFF
OFF
NC input, no verification, reversal while opening and closing (BAR)
OFF
ON
NC input, no verification, reversal only when closing, stop when
opening (BAR CL)
ON
OFF
NC input, with verification, reversal while opening and closing (BAR
TEST)
ON
ON
NC input, with verification, reversal only when closing, stop when
opening (BAR CL TEST)
OFF
OFF
8K2 input, reversal when opening and closing (BAR 8K2)
OFF
ON
8K2 input, reversal only when closing, stop when opening (BAR CL 8K2)
ON
OFF
---
ON
ON
---
-20 / +55°C
mains/LV 3750V~ for 1 minute
400W+400W
24V ~ (demand max. 0,2A)
see Fig. F1-F2
120V~ 40W max
230V~ 40W max
see Fig. B
frequency 433.92MHz
TRIMMER + DIP SWITCH
4 billion
8 s.
120s
23
ALENA SW2 CPEM -