Drain Piping Work - Toshiba MMC-AP0151H Manual De Instalación

Ocultar thumbs Ver también para MMC-AP0151H:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 104
2) Hang the unit to the hanging bolt as shown the
figure below.
3) As shown in the figure below, fix the ceiling material
securely with the double nuts.
4

DRAIN PIPING WORK

• Following the Installation Manual, perform the drain piping work so that water is properly
drained, and apply a heat insulation so as not to cause a dew. Inappropriate piping work
may result in water leakage in the room and wet of furniture.
Pipe material/Insulator and size
The following materials for piping work and insulating process are procured locally.
Hard vinyl chloride pipe socket for VP20
Pipe material
Hard vinyl chloride pipe VP20
(Outer diameter Ø26mm)
Foamed polyethylene foam, thickness:
Insulator
10mm or more
• The ceiling surface may not be
horizontal. Be sure to confirm that width
and depth directions are level.
Installation of remote controller
(Sold separately)
For installation of the wired remote controller, follow
the Installation Manual attached with the remote
controller.
For installation of the wireless remote controller, follow
to the Installation Manual attached to the wireless
remote controller.
• Do not put the remote controller on the place where
is exposed to direct sunlight or near a stove, etc.
• Operate the remote controller, check the indoor unit
surely receives the signal, and then install the
remote controller. (Wireless type)
• Install the remote controller 1m apart from the
devices such as TV or stereo. (Image may be
disturbed or noise may be output.) (Wireless type)
CAUTION
8
REQUIREMENT