150
Slave Address
Select slave mode on device, for serial communication.
1..254.
: 247.
Default
151
Slave Baud Rate
Selects baudrate for serial communication
1200 bit/s
1 .2 k
2400 bit/s
2 . 4 k
4800 bit/s
4.8 k
9600 bit/s
9.6 k
19200 bit/s (
19.2 k
28800 bit/s
28.8 k
38400 bit/s
38. 4 k
57600 bit/s
57.6 k
115200 bit/s
1 15.2k
152
Slave Serial Port Format
Selects the format used by the controller during modbus RTU serial communication.
8 bit, no parity, 1 stop bit (
8-N-1
8 bit, even parity, 1 stop bit
8-E-1
8 bit, odd parity, 1 stop bit
8-o-1
8 bit, no parity, 2 stop bit
8-N-2
8 bit, even parity, 2 stop bit
8-E-2
8 bit, odd parity, 2 stop bit
8-o-2
153
Serial Delay
Sets the serial delay
0...100 ms.
Default
154
Off Line
Selects the off-line time frame. If there is no serial communication during this period, the controller
switches-off the command output
0
Offline disabled (
0.1-600.0 tenths of second.
155÷159
Reserved Parameters - Group K
Reserved parameters - Group K.
11.l
GROUP L -
160
Modbus Master
Modbus in master mode, disabled. (
diSAb.
Modbus in master mode, enabled.
EnAb.
Modbus in master mode, enabled for handling AMPER-0-RS.
En.CT
Modbus in master mode, enabled for handling AMPER-0-RS
En.CT .A.
as amperometer (the current will be the process).
161
Target Address
Sets the slave number address used for serial communication
0..254.
: 1.
Default
162
Master Baud Rate
Sets the baud rate used for serial communication while the device is operating in Master mode
1200 bit/s
1 .2 k
2400 bit/s
2 . 4 k
4800 bit/s
4.8 k
9600 bit/s
9.6 k
19200 bit/s (
19.2 k
28800 bit/s
28.8 k
38400 bit/s
38. 4 k
57600 bit/s
57.6 k
115200 bit/s
1 15.2k
34
)
Default
Default
: 5 ms.
)
Default
– Master Serial Port
)
Default
)
(only available on xxxxxx-T)
)
Default