MONOSPLIT INSTALLATION TECHNICAL SPECIFICATIONS
OUTDOOR UNIT MODEL
Liquid pipe diameter
Gas pipe diameter
Maximum length of pipe with standard charge
Maximum pipe length*
Standard charge
Extra gas recharge
Maximum diff erence in height
between internal
and external unit**
Type of refrigerant
GWP
MULTISPLIT INSTALLATION TECHNICAL SPECIFICATIONS
OUTDOOR UNIT MODEL
Liquid pipe diameter
Gas pipe diameter
Maximum pipe length for single internal unit
with standard charge
Maximum pipe length for single internal unit*
Maximum total length of piping (sum of internal units)*
Standard charge
Extra gas recharge
Maximum diff erence in height between internal and ex-
ternal unit (internal unit just above the external unit)**
Maximum diff erence in height between internal and ex-
ternal unit (internal unit just below the external unit)**
Maximum diff erence in height between internal units
Type of refrigerant
GWP
(*)
at the maximum distance, effi ciency is approximately 90%.
(**) with a diff erence in height over 5 m, we recommend you include a trap.
PRIOS R32 25 MD0-O
inches
1/4
inches
3/8
m
5
m
25
kg
0,5
t CO eq.
0,34
g/m
12
m
10
R32
675
DUAL 50
XD0C-O
inches
2x 1/4
inches
2x 3/8
m
5
m
25
m
40
kg
1,3
t CO eq.
0,88
g/m
15
m
15
m
10
m
10
R32
675
PRIOS R32 35 MD0-O
PRIOS R32 50 MD0-O
1/4
3/8
5
25
0,5
0,34
12
10
R32
675
TRIAL 80
QUAD 110
XD0C-O
XD0C-O
3x 1/4
4x 1/4
3x 3/8
3x 3/8+ 1x1/2 4x 3/8 + 1x 1/2
5
5
30
35
60
80
1,57
2,1
1,06
1,42
15
15
15
15
10
10
10
10
R32
R32
675
675
/ 51
GB
1/4
1/2
5
30
1
0,68
12
20
R32
675
PENTA 121
XD0C-O
5x 1/4
5
35
80
2,4
1,62
15
15
10
10
R32
675