Options - HTW ECO THERMAL PLUS Manual De Usuario/Instalador

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

6.4.3 Schedule check
schedule check can only check the weekly schedule.
Go to ''MENU'' > ''SCHEDULE'' >''SCHEDULE' CHECK''.
Press''OK''. The following page will appear:
SCHEDULE
WEEKLY
SCHEDULE
TIMER
SCHEDULE
CHECK
WEEKLY SCHEDULE CHECK
ENTER
OK
WEEKLY SCHEDULE CHECK
DAY
NO
MODE SET START END
T1
HEAT
0℃
T2
HEAT
0℃
T3
HEAT
0℃
MON
T4
HEAT
0℃
T5
HEAT
0℃
T6
HEAT
0℃
Press ''▼''、 ''▲'' , the timer from Monday to Sunday will
appear:
6.4.4 CANCEL TIMER
Go to ''MENU'' > ''SCHEDULE'' >''CANCEL TIMER''.
Press''OK''. The following page will appear:
SCHEDULE
WEEKLY
SCHEDULE
TIMER
SCHEDULE
CHECK
Do you want to cancel the
timer and weekly schedule?
NO
ENTER
OK
Use ''◄ ''、 ''► ''、 ''▼''、 ''▲''to move to "YES", press
"OK" to cancel timer. If you want to exit CANCEL TIMER,
press "BACK".
If TIMER or WEEKLY SCHEDULE is activated, timer
icon ''
'' or weekly schedule icon ''
the home page.
CANCLE
TIMER
00:00 00:00
00:00 00:00
00:00 00:00
00:00 00:00
00:00 00:00
00:00 00:00
CANCLE
TIMER
YES
'' will display on
7
15
If TIMER or WEEKLY SCHEDULE is canceled, icon''
or ''
'' will disappear on the home page.
7
INFORMATION
i
You have to reset TIMER/WEEKLY SCHEDULE,
if you change the WATER FLOW TEMP. to the
ROOM TEMP. or you change the ROOM TEMP.
to the WATER FLOW TEMP.
The TIMER or WEEKLY SCHEDULE is invalid, if
ROOM THERMOSTAT is effect.
INFORMATION
i
The ECO has the highest priority, the TIMER or
WEEKLY SCHEDULE has the second priority
and the PRESET TEMP. or WEATHER TEMP.
SET has the lowest priority.
The PRESET TEMP. or WEATHER TEMP. SET
becomes invalid, when we set the ECO valid. We
must reset the PRESET TEMP. or WEATHER
TEMP. SET when we set the ECO invalid.
TIMER or WEEKLY SCHEDULE is invalid when
ECO is valid. TIMER or WEEKLY SCHEDULE is
activated when the ECO is not running.
TIMER and WEEKLY SCHEDULE are on the
same priority. The later setting function is valid.
The PRESET TEMP. becomes invalid when
TIMER or WEEKLY SCHEDULE is valid. The
WEATHER TEMP. SET is not affected by the
setting of TIMER or WEEKLY SCHEDULE.
PRSET TEMP. and WATHER TEMP.SET are
on the same priority. The later setting function is
valid.
INFORMATION
i
All about the time set items(PRESET TEMP. 、
ECO 、 DISINFECT、 DHW PUMP 、 TIMER、
WEEKLY SCHEDULE、SILENCE MODE 、
HOLIDAY HOME), the ON/OFF of the
corresponding function can be activated from
the start time to the end time.

6.5 Options

OPTIONS menu contents as following:
1) SILENT MODE
2) HOLIDAY AWAY
3) HOLIDAY HOME
4) BACKUP HEATER
''
Tabla de contenido
loading