4
Installation
Water Circulation Pump Characteristics
EHSC, ERSC series
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
0.0
5.0
10.0
15.0
20.0
25.0
Flow rate [L/min]
<Figure 4.3.4>
EHPX series * (with PUHZ-W50)
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
0.0
5.0
10.0
15.0
20.0
25.0
Flow rate [L/min]
<Figure 4.3.5>
* For installation of EHPX series, set its pump speed with a pressure drop between the hydrobox and the outdoor unit factored into the external static pressure.
Safety Device Connections
The hydrobox contains a pressure relief valve. (see <Figure 4.3.8>) The con-
nection size is G/2" female. The installer MUST connect appropriate discharge
pipework from this valve in accordance with local and national regulations.
Failure to do so will result in discharge from the pressure relief valve directly into
the hydrobox and cause serious damage to the product.
All pipework used should be capable of withstanding discharge of hot water.
Relief valves should NOT be used for any other purpose, and their discharges
should terminate in a safe and appropriate manner in accordance with local regu-
lation requirements.
Note: Beware that the manometer and the pressure relief valve are NOT
strained on its capillary side and on its inlet side respectively.
If a pressure relief valve is added, it is essential that no check valve
or isolation valve is fitted between the hydrobox connection and the
added pressure relief valve (safety matter).
Piping diagram for 2-zone temperature control
Connect the pipe work and field supplied parts according to the relevant circuit
diagram shown in Section 3. Technical Information, of this manual.
For more details on wiring, refer to "5.3 Wiring for 2-zone temperature controls".
Note: Do not install the thermistors on the mixing tank. This could affect
correct monitoring of flow and return temperatures through each
zone.
Install the Zone2 flow temp. thermistor (THW8) near the mixing valve.
7
Speed 5 (Default)
Speed 4
Speed 3
Speed 2
Speed
30.0
35.0
40.0
EHPX series * (with PUHZ-W85)
80.0
Speed 5 (Default)
70.0
Speed 4
Speed 3
60.0
Speed 2
50.0
Speed
40.0
30.0
20.0
10.0
0.0
30.0
35.0
40.0
0.0
5.0
Speed 5 (Default)
Speed 4
Speed 3
Speed 2
Speed
10.0
15.0
20.0
25.0
30.0
35.0
40.0
Flow rate [L/min]
<Figure 4.3.6>
EHPX series * (with PUHZ-HW2/40)
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
0.0
5.0
10.0
15.0
20.0
25.0
Flow rate [L/min]
<Figure 4.3.7>
Factory-fitted pressure relief valve
(G/2" female connection)
Discharge to drain
(pipe MUST be fitted by installer).
<Figure 4.3.8>
Speed 5 (Default)
Speed 4
Speed 3
Speed 2
Speed
30.0
35.0
40.0