TEC29EV
Displays
No. in
fig. 3,
Description
page 4
6
AC supply
7
Constant output
8
Operating hours
9
DC voltage
10
Messages
8
Operating the generator
A
NOTICE!
Do not run the generator over 70 % of the maximum constant out-
put for the first 50 operating hours (run-in phase).
I
NOTE
Run the generator at a maximum of approx. 75 % of the maximum
continuous load after the run-in phase.
By doing this you can prolong the service life of the generator and
maximise its efficiency.
8.1
Basic notes on operation
!
CAUTION! Beware of injury
Do not insert your fingers or objects into the air nozzles or the
intake grille.
Please note the following basic information:
Always check the oil level before use (chapter "Checking the oil level" on
page 19).
Even small overloads in the long-run will cause the cut-out switch to
trigger.
Leave the generator running for a few minutes after use without any
consumers before stopping it.
EN
Operating the generator
Actual voltage output
Current capacity of connected consumer
Time the generator is in operation
Battery voltage
Status reports of the generator (see
chapter "Display messages" on page 17)
15