5.4 MANUAL START OF MOTOR/PRIMING

This procedure is applicable when you want to manually start the system or prime the pump.
It is possible to manually start the motor by pressing the following sequence of buttons:
Buttons sequence with pump off, last button pressed for 10 seconds.
ATTENTION
During manual start-up, the motor rotates at maximum speed and the pressure control is not activated, therefore the pump
reaches its maximum pressure.
ATTENTION
Ensure there is water inside the pump unit, otherwise the pump seal will be destroyed.
NOME
DESCRIZIONE
PARAMETRO
Subtract this figure from the set point to obtain pressure when
the motor is started-up. In other words, the motor starts-up
Pressure threshold
when pressure reaches the set point value minus the threshold
value (BAR).
Indicates minimum system pressure, a lack of water alarm will be
Water alarm pressure
generated under this threshold value Set to zero to disable this
function.
Waiting time between the first lack of water reading and first
attempt to automatically restart the system (minutes). The module
1st start-up
will not attempt to
restart if this parameter is set to zero.
Waiting time between the first restart and the second attempt to
2nd restart
automatically restart the system (minutes).
Waiting time between the second restart and the third attempt to
3rd restart
automatically restart the system (minutes).
Waiting time between the third restart and the fourth attempt to
4th restart
automatically restart the system (minutes).
Parameter used to define how the restarting mechanism works. If
set to FIN, the module will go into a definitive alarm after the fourth
Restart type
attempt. If sent to CICL, it will attempt to restart indefinitely using
the interval specified during the fourth attempt.
Waiting time after restarting within which pressure must return to
Intervention time
above the minimum threshold level for lack of water. (seconds)
Hours running
Number of hours the pump has been running.
Parameter indicating the amount of time a pump must run for.
Once this value has been reached, the pump will stop and a second
pump will
commence working. This parameter is expressed in minutes until
Exchange time
it reaches 60, after which it is expressed in hours. The difference is
indicated by the presence
of an "H" for hours and an "M" for minutes.
Must be set to primary for a unit or for twin pumps.
Pumps are exchanged once the SCAT parameter has been
reached:
T1: The active pump is switched off first, before the second pump
Exchange time mode
starts up
T2: The second pump is switched off first, before the first pump
starts-up.
PWM frequency
Frequency of the PWM which controls the motor.
Amount of time the pump is inactive. Once this amount of time
has expired, the pump will start up for 15 seconds at maximum
frequency. Then, the frequency will be slowly lowered until the
Anti-locking
minimum set frequency is obtained. This parameter is expressed
in minutes until it reaches 60, after which it is expressed in hours.
The difference is indicated by the presence of an "H" for hours and
an "M" for minutes.
EN
DEF
MIN
MAX
0,3
0,1
0,5
0,5
0
1
1
0
1440
5
0
1440
60
0
1440
720
0
1440