EN
5.3.4 INSTALLATION PARAMETERS
Key sequence to access the installation menu, last button pressed for 10 seconds.
•
During the modification of the
parameters, the symbol
display lights up
•
Use the MODE key to change various
parameters
DESCR.
MENU
DISPLAY
TIP O
SCA
INSTALLATION
PARAMETERS
INF F
SUP F
ANP F
SUP S
INF S
OFF P
SPE T
32
•
With the buttons it is possible to
on the
modify the values
PARAMETER
DESCRIPTION
NAME
Identifies whether the pump is part of a unit or whether it
is a single pump, possible values:
•
NCON: pump not configured (factory setting)
Pump type
•
SING: single pump
•
PRI: primary or master pump for a unit
•
SEC: secondary or slave pump for a unit
This parameter indicates the mode used to change pumps
when the pump is part of a unit (PRI, SEC).
•
CH01: Indicates that the first pump to come on at the next
request for water will be the one which started-up second or
which did not start-up during the last cycle. The second pump
cannot support the first in this mode
(BOOSTER setting).
•
CH02: Indicates that the first pump to come on at the next
request for water will be the one which did not start up during
the last cycle. The second pump cannot support the first in
this mode.
•
CH03: Indicates that the first pump to come on at the next
Type of exchange
request for water will be the one which has run for the least
amount of time (see functioning hours parameter). The second
pump cannot support the first in this mode (BOOSTER setting).
•
CH04: Indicates that the first pump to come on at the next
request for water will be the one which has run for the least
amount of time (see functioning hours parameter). The second
pump cannot support the first in this mode.
•
CH05: In this setting, the first pump to start-up is the one
entered as the primary pump in the "type of pump" parameter.
The second pump can
support the first in this mode; however, the cyclical function is
not available.
Minimum frequency
Parameter defining minimum motor rotation frequency.
Maximum frequency
Parameter defining maximum motor rotation frequency.
Parameter defining the speed with which the motor responds to
Reactivity factor
changes in pressure. The lower the setting the faster the motor' s
response.
Bottom scale sensor
Parameter defining the sensor at the bottom of the scale (in bar).
Zero sensor
Minimum value read by the sensor (zero).
Offset sensor
Use to enter an offset value for the pressure sensor.
Interval of time during which pressure must remain stable (+/- 0.1
Switching off time
Bar) with a rotation lower than the average switching off frequency
+ 10 to trigger the motor shutdown cycle (seconds).
•
To memorize the values press the
button "SET". The symbol
The words "REC" will appear on the
screen for a few seconds to show that
the data has been saved
DEF
MIN
SING
N.A.
01
01
30
20
50
40
15
1
10
2
0,6
0
0
0
10
3
.
MAX
N.A.
05
40
60
50
30
1
10,0
50