Technical Data - ABB CP-C.1 Serie Instrucciones De Servicio Y De Montaje

Tabla de contenido

Technical data

o
Data at T a = 25
C, U in = 230 V AC and rated values, unless otherwise indicated
Type
Input circuit - Supply circuit
Rated input voltage U
in
Input voltage range
Frequency range AC
Typ. input current
Typical power consumption
Hold-up time
Recommended backup fuse for wire
protection at 1.5 mm²
Output circuit - Power output
Rated output power
Rated output voltage
Adjustment range of the output voltage
Rated output current I
r
Power reserve current
Current limiting at short circuit
Derating of the output current
Residual ripple and switching peaks
acc. to IEC/EN 61204, class A
Resistance to reverse feed
General data
Efficiency
Degree of protection (IEC/EN 60529)
Protection class (IEC/EN 61140)
Environmental data
Ambient temperature ranges
Isolation data
Pollution degree
Environment acc. to CAN/CSA 22.1 No. 107.1
Overvoltage category (EN 50178)
Overvoltage category (IEC/EN 60950-1)
* CP-C.1....-C:
-25 °C -> -40 °C
at 115 V AC
at 230 V AC
at 230 V AC
at 115 V AC
at 230 V AC
1 pole miniature circuit breaker ABB type S 200, with B or C characteristic,
*
-25 °C
T
60 °C
a
*
7.5 A continuously
-25 °C
T
40 °C
a
60 °C < T
70 °C
a
BW=20 MHz
operation
rated load
storage
< 2000 m
2000-5000 m
< 2000 m
2000-5000 m
24 V / 5.0 A
24 V / 10.0 A
100-240 V AC /
90-300 V DC
85-264 V AC /
90-300 V DC
1.1 A
0.6 A
132 W
min. 50 ms
min. 50 ms
max. rating 16 A
120 W
22.5-28.5 V DC
5.0 A
15.0 A continuously
7.6 A
up to 93 %
housing / terminal: IP20
-25
-25
-40...+85 °C
Controlled environment
24 V / 20.0 A
L, N
100-240 V AC /
90-250 V DC
85-264 V AC /
90-250 V DC
45-65 Hz
2.3 A
1.2 A
256 W
min. 40 ms
min. 40 ms
L+, L-
240 W
24 V DC
10.0 A
26.0 A continuously
15.5 A
2.5 %/K
< 120 mV
pp
35 V DC
up to 94 %
up to 94 %
I
*
...+70 °C
*
...+60 °C
2
III
II
II
I
4.6 A
2.3 A
508 W
min. 40 ms
min. 40 ms
480 W
20.0 A
27.7 A
16