Required Tools - S&P PULSE 160 Manual De Instrucciones

Ocultar thumbs Ver también para PULSE 160:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Article
Item
name
1
Internal air output
2
Dust fi lter
3
Fan unit
4
Heat exchanger unit
PULSE
160
5
Pre fi lter
6
Foam support ring
7
Mounting tube 500 mm
8
Outside air outlet
3.2. PULSE CONTROL PRO COMPONENTS
Article
Item
name
Panel de operaciones del
1
PULSE CONTROL PRO
PULSE
2
Marco
CONTROL
3
Unidad de alimentación
PRO
Caja de mecanismo del
4
PULSE CONTROL PRO
3.3. DIMENSIONES
16
Content
Num.
1
1
1
2
1
1
1
1
Content
Num.
1
1
1
1

3.4. REQUIRED TOOLS

The following equipment is needed to install the
PULSE 160:
• Core drill with a Ø 162 mm bit
• Sabre saw for sawing plastic
• Mounting adhesive / sealant to fi x the mounting
tube in place
• Hammer and chisel for cable ducts / slits
3.5. POSITIONING
The best position for the PULSE 160 is determined
in the project planning phase. Please pay atten-
tion to the minimum distances, as otherwise no
guarantee can be given that the units will function
properly.
Minimum distance to the ceiling and to the fl oor
The minimum distance to
the ceiling must not be less
than 300 mm, and to the
fl oor not less than 1000 mm.
Minimum distance to other objects (e.g. windows
or doors) or walls
› 150 mm
The distance to other
building elements such as
windows, doors or other
walls should be at least 150
mm, both inside and outside.
Minimum distance between two PULSE 160 units
on the same wall
› 1000 mm
The distance between two
units, whether horizontally
or vertically, should not be
less than 1000 mm.
Minimum distance between two PULSE 160 units
installed on two neighbouring walls
When installing units on
neighbouring walls, make
sure that each unit is at least
1000 mm away from the
other wall. In addition, the
diagonal distance between
the two units must not be
less than 1400 mm.
Tabla de contenido
loading

Tabla de contenido