8. TROUBLESHOOTING
Fault
Cause
Control unit
operating in "full-
blast" mode.
Fan unit not
Fan unit not wor-
changing
king properly.
direction.
Control unit /
power supply not
working properly.
No power.
Installation error. • Check the ca-
Fan unit not
functioning.
Fan unit not wor-
king properly.
Control unit /
power supply not
working properly.
Installation
error.
Control
unit not
functioning.
Power supply not
working properly.
Control unit not
working properly.
Rotor blades
dirty.
Dirt or other
elements in the
Noise level
fan.
higher than
normal when
operating in
Distance between
normal mode.
the heat exchan-
ger unit and fan
unit too small.
Fan speed too
high.
24
Fault
Remedy
• Set the controls
to eco-mode
(heat recovery).
• Replace the fan
unit.
Low level of
• Replace the con-
airfl ow.
trol unit / power
supply.
• Restore power
supply.
bling and wiring.
• Check whether
all plugs have
been properly
connected.
Incoming air
is cold.
• Replace the fan
unit.
• Replace the con-
trol unit / power
supply.

9. TECHNICAL ASSISTANCE

• Check the ca-
If the product fails to turn on or it operates ab-
bling and wiring.
normally or is abnormally noisy, disconnect the
• Check that the
control unit
product from the power by positioning the "0/1"
is installed
switch on the side of the main unit to "0". Contact
correctly.
your dealer immediately and request technical as-
sistance from our qualifi ed staff.
• Replace the
power supply.
• Replace the
10. PUTTING OUT OF SERVICE AND RECYCLING
control unit.
• Clean the rotor
blades.
• Clean the ventila-
tion unit.
• Remove dirt or
your device is also labeled with this symbol, please
other elements.
take it to the nearest. Waste Management Plant at
• Clean the ventila-
the end of its serviceable life.
tion unit.
If you have any queries about S&P products, plea-
• Check the
se contact our After-Sales Service Network if you
spacers on the
fan unit.
are in Spain or your local S&P dealer in any other
• Increase the
country. If in doubt, please visit our Web-page
distance.
www.solerpalau.com
• Switch to a lower
speed.
Cause
Remedy
Inside cover is
• Open the inside
shut.
Filter clogged up. • Clean the fi lter or
Heat exchanger
• Clean the heat
unit dirty.
• Clean the ventila-
Fan speed too
• Switch to a
low.
Units not working
• Check that the
in conjunction
with each other
(in pairs).
Control unit is
• Select Eco-mode
operating in "full-
blast" mode.
Heat
• Insert the heat
exchanger unit
missing.
EC legislation and our consideration of
future generations mean that we should
always recycle material where possible;
please do not forget to deposit all packa-
ging in the appropriate recycling bins. If
cover.
replace it.
exchanger unit.
tion unit.
higher speed.
units are co-
rrectly connected
to the control
unit.
(heat recovery) at
the control unit.
exchanger.