4- Safety system regulation
GPG 70, GPG-D 70, GPG 200 M, GPG-D 200 M, GPG 200 T,
Models
GPG-D 200 T, GPG 500 T, GPG-D 500 T
1. Remove the plate that provides access to the regulator.
2. Turn the burner/s on to produce the standard maximum fuel consumption.
3. Provoke a leakage in the discharge point equivalent to 10 l/h approx.
4. At the moment when the manometer indicates the minimum working pressure
5. Seal the leakage in the discharge point, rearm the set (pressing the push
Directions
for use
6. Provoke the same leakage another time when the pump is standing still. Then,
7.
5- Pump Selector
In the case of double GPG sets, the switch installed in the electrical panel is used for manually
determining which pump has to work.
Maintenance and conservation
For double sets, periodically alternate the service pump, opening and closing the corresponding
valve and using the electric panel selector.
Manual de instrucciones/Manual/Manuel d'instructions "GPG/GPG-D"
(right before the pump starts up), slightly turn the regulator anticlockwise until
the indicator light switches on showing the set is blocked.
button) and check the operation is correct. In other words, the start-up and
shutdown work without blocking.
when the pressure decreases, right before the set starts back up, the indicator
blocking light should switch on. If that's not the case, it means the leak was not
big enough or the regulator is not properly closed.
Finally, place the plate in front of the regulator to avoid any manipulation.