Siemens SITRANS TF2 Instrucciones De Servicio página 40

Transmisor de temperatura para montaje en campo con lcd y pt100
Ocultar thumbs Ver también para SITRANS TF2:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Technical description
Function
Mode
Offset
9
higher
Upper current
10
higher
saturation
limit
Lower current
11
higher
saturation
limit
Electrical
12
higher
damping
Table 1
Parameter setting
(Continuation)
The following applies to all modes:
The value last displayed will be saved when you quit the corresponding mode.
All sizes are calculated and displayed according to the unit set in mode 4.
Exception: current saturation limits.
Inputting the password (mode 2)
Once the password has been input, modes 4 to 12 can be accessed. The password
is "99".
Procedure:
Use the M button to set mode 2
Use the
If the password is correct, the other modes will be accessible.
If the password is incorrect, the unit will jump back to mode 1.
40
Key function
M
lower
M10
lower
M11
lower
M12
⇒ M1 Time constant T
lower
button or the
button to select the password
Operating instructions
Display,
explanatory comments:
Output value = value at input +
offset
(Value entry between
–100 °C and 100 °C; note unit
selected)
Factory setting 0 °C
Upper current saturation
Setting range
20.5 to 23 mA
Factory setting 20.5 mA
Lower current saturation
Setting range
3.6 to 3.8 mA
Factory setting 3.8 mA
in s; setting
63
range 0.1 – 100 s
(Factory setting 0.2 s)
SITRANS TF2
A5E00263328-02
Tabla de contenido
loading

Este manual también es adecuado para:

7ng3140

Tabla de contenido