4
Mounting instructions
C16M...
S lt should be ensured that the mounting/siting surfaces
are clean, flat and level. Depending on the Installation
circumstances, any levelling error can be compen
sated for example by suitable wedges and compen
sating plates (permanently welded) or by the grinding
away the mounting surface. On no account must the
module plates be ground.
Notice
On no account must the module plates be ground.
S The foundation/base frame must be sufficiently stiff so
that no impermissible deformations (e.g. deflections)
occur on loading.
S In order to keep the mounting as free of straining
forces as possible, the fastening holes on the base
frame and the tank joint must be sufficiently in align
ment. Same means to the bore of the anti‐liftoff de
vice.
S Uniform loading on the support points should be pro
vided where possible. Correct adjustment of the
height on the supporting points must be ensured
(have compensating shims ready). This is especially
important for statically undefined supports.
A1268-3.0 HBM: public
Mounting instructions
9