Danfoss Optyma Semi-Hermetic Serie Manual De Uso página 4

Idiomas disponibles

Idiomas disponibles

Instructions
Instructions - Optyma™ Semi-Hermetic
A
B
C
D
E
F
G
A: Model
B: Code number
C: Serial number and bar code
D: Compressor information
E: Fan motor information
F: HP pressure test
G: LP pressure test
H: Aparent power
I: Pactive power
J: Rated Load Amperage RLA
K: Maximum Continuous Current MCC
Picture 2
1 – Introduction
These instructions pertain to Optyma™ Semi-
hermetic condensing units (R404A/R507, R22)
used for refrigeration systems. They provide ne-
cessary information regarding safety and proper
usage of this product
The condensing unit includes following:
• Semi-hermetic pack compressors
• Microchannel heat exchanger
• Adjustable low Pressure switch
• Fix high pressures cartridge
• Service valves Suction/ liquid
• Filter drier
• Cranckcase heater for compressor
• Receiver with stop valve
• Sight glass
• Fully pre-wired electrical panel (Contactor)
2 – Handling and storage
• It is recommended not to open the packaging
before the unit is at the final place for installation.
• Handle the unit with care. The packaging al-
lows for the use of a forklift or pallet jack. Use
appropriate and safe lifting equipment.
• Store and transport the unit in an upright position.
• Store the unit between -35°C and 50°C.
• Don't expose the packaging to rain or corrosive
atmosphere.
4 | © Danfoss | DCS (CC) | 2018.10
H
I
J
K
L: Cable entry ports
M: Suction port
N: Liquid port
O: Microchannel heat exchanger
Picture 4
Mounting bolts and
vibra stop (not supplied)
Picture 3
• After unpacking, check that the unit is com-
plete and undamaged.
3 – Installation precautions
Do not braze as long the condensing unit is
under pressure.
Never place the unit in a flammable atmosphere
Place the unit in such a way that it is not blocking
or hindering walking areas, doors, windows or similar.
• Ensure adequate space around the unit for air
circulation and to open doors. Refer to picture1
for minimal values of distance to walls.
• Avoid installing the unit in locations which are daily
exposed to direct sunshine for longer periods.
• Avoid installing the unit in aggressive and dus-
ty environments.
• Ensure a foundation with horizontal surface
(less than 3° slope), strong and stable enough
to carry the entire unit weight and to eliminate
vibrations and interference.
• The unit ambient temperature may not exceed
50°C during off-cycle.
• Ensure that the power supply corresponds to
the unit characteristics (see nameplate).
• When installing units for HFC refrigerants, use
equipment specifically reserved for HFC refri-
gerants which was never used for CFC or HCFC
refrigerants.
Picture 1 : Minimum mounting distances
P
Q
R
[mm]
[mm]
[mm]
250
650
550
Installation and servicing of the
condensing
units
personnel
only.
instructions
and
sound
engineering practice relating to installation,
commissioning, maintenance and service.
The condensing unit must only be used for
its designed purpose(s) and within its scope of
application.
Under all circumstances, the EN378 (or
other applicable local safety regulation)
requirements must be fulfilled.
The condensing unit is delivered under nitro-
gen gas pressure (1 bar) and hence it cannot
be connected as it is; refer to the «installation»
section for further details.
The condensing unit must be handled with cau-
tion in the vertical position (maximum offset
from the vertical : 15°)
• Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The suction piping connected to the compres-
sor must be flexible in 3 dimensions to dampen
vibrations. Furthermore piping has to be done
in such a way that oil return for the compres-
sor is ensured and the risk of liquid slug over in
compressor is eliminated.
4 – Installation
• The unit must be securely installed on a stable
and rigid support, and fixed from the begin-
ning. See picture 2.
• It is recommended to install the unit on rub-
ber grommets or vibration dampers (not sup-
plied).
• Slowly release the nitrogen holding charge
through the schrader port.
• Connect the unit to the system as soon as pos-
sible to avoid oil contamination from ambient
moisture.
• Avoid material entering into the system while
cutting tubes. Never drill holes where burrs
cannot be removed.
• Braze with great care using state-of-the-art tech-
nique and vent piping with nitrogen gas flow.
• Connect the required safety and control de-
FRCC.PI.060.A1.02
S
[mm]
550
by
qualified
Follow
these
refrigeration
loading