F02-Start, stop, forward/reverse, brake function parameter group
Function
Name
Code
F02.00
Start running mode
F02.01
Starting delay time
F02.02
Starting frequency
F02.03
Starting frequency
duration time
F02.04
DC braking current when
starting
F02.05
DC braking time when
starting
F02.06
Speed track starting
frequency selection
F02.07
Speed track auxiliary
starting frequency
F02.08
Speed track starting
waiting time
F02.09
Speed track current
control coefficient
F02.10
Speed track searching
speed time
F02.11
Stop mode
F02.12
Deceleration stop holding
frequency
F02.13
Deceleration stop holding
time
F02.14
Stop DC braking starting
frequency
F02.15
stop DC braking waiting
time
F02.16
Stop DC braking current
F02.17
Stop DC braking time
F02.18
Stop auxiliary braking
current
F02.19
Stop auxiliary braking
time
F02.20
Forward/reverse dead
zone time
Set Range
0: Start from starting frequency
1: First brake and then start from starting
frequency
2: Start by revolving speed tracking
0.0~60.0s
0.0~10.00Hz
0.0~60.0s
0.0~100.0% (G type inverter rated current)
0.0~30.0s
0: Current setting frequency.
1: Running frequency before power down.
2: Speed track auxiliary starting frequency.
0.00Hz~upper limit frequency
0.00~10.00s
1~20
0.1~30.0 (V/F control unit is 1 second; SVC
control unit is 0.1 second)
0: Deceleration stop.
1: Free stop
2: Deceleration + DC braking stop.
0.00~upper limit frequency (This parameter is
only valid for stop mode 0.)
0.00~10.00s
0.00~15.00Hz
0.00~30.00s
0.0~100.0% (G type inverter rated current)
0.0~30.0s
0.0~100.0% (G type inverter rated current)
0.0~100.0s
0.0~3600.0s
6. Function parameter schedule graph
Min.
Factory
Unit
Default
1
0.1s
0.01Hz
0.00Hz
0.1s
0.1%
30.0%
0.1s
1
0.01Hz
10.00Hz
0.01s
0.10s
1
0.1
1
0.01Hz
0.00Hz
0.01s
0.00s
0.01Hz
0.00Hz
0.01s
0.00s
0.1%
0.1s
0.1%
0.1s
0.1s
Modifi-
cation
0
×
0.0s
×
×
0.0s
×
×
0.0s
×
2
×
×
×
2
×
4.0
×
0
o
×
×
×
×
0.0%
×
0.0s
×
0.0%
×
0.0s
×
0.0s
×
175