Storage
-40 to 70°C
10 to 90 relative humidity
Altitude: < 2000 m
7.5. CONSTRUCTION SPECIFICATIONS
Overall dimensions of the instrument (L x W x H): 270 x 250 x 180 mm
Weight: approximately 4.3 kg
7.6. COMPLIANCE WITH INTERNATIONAL STANDARDS
Electrical safety as per: IEC 61010-1, IEC 61557
Double insulation
Pollution level: 2
Measurement category: III
Maximum voltage relative to earth: 1000 V (2500 V in measurement category I)
7.6.1. ELECTROMAGNETIC COMPATIBILITY
Emissions and immunity in an industrial setting compliant with EN61326-1
7.6.2. MECHANICAL PROTECTIONS
IP 53 as per IEC 60529
IK 04 as per IEC 50102
7.7. VARIATIONS WITHIN DOMAIN OF USE
Infl uence
quantity
Battery voltage
Temperature
-10 ... +55°C
Humidity
10 ... 80% HR
Frequency
15 ... 500 Hz
AC voltage
superimposed on test
voltage
(1): The DAR, PI and DD terms and the capacitance and leakage current measurements are included in
the quantity "M ".
Range of
Quantity
infl uence
infl uenced
V
9 ... 12 V
M
V
M
V
M (10 k ... 40 G )
M (40 G ... 10 T )
V
M
0 ... 20%Un
109
Infl uence
(1)
Typical
< 1 ct
< 1 ct
0.15%/10°C
0.20%/10°C
0.2%
0.,2%
0.3%
3%
0.1%/% Un
Maximum
2 ct
3 ct
0,3%/10°C +1 ct
1%/10°C + 2 ct
1% +2 ct
1% +5 ct
15% +5 ct
0.5% +1 ct
0.5%/% Un +5 ct