3.6 Adjusting the bypass

To pool
Out
How to get the optimum water flow:
Please turn on the heat pump under heating function, firstly close the by-pass then open it slowly to start the heat
pump (the heat pump can't start running when the water flow is insufficient).
Continue to adjust the by-pass, at the meantime to check the Inlet water temp. & Outlet water temp, it will be
optimum when the difference is around 2 degrees.
Drain out the water in winter for the units without drainage outlet in heat exchanger
Turn off the heat pump and be sure that it disconnected power
Turn off the water pump
-
Close the valves 1 and 2
Open the valve 4
-
Allow water to drain out over a long period until heat pump is fully drained.
NOTE: It need to close the valve 4 before turn on the heat pump.
Heat Pump
Use the following procedure to adjust the
bypass:
1. Open Valve 1 & 2 half way.
2. Close valve 2 until control shows
NO Or EE3 screen.
3. Slowly open Valve 2 until pool
Temp shows on screen.
4. If it shows 'ON' or 'EE3' on display,
it means the water flow into heat
pump is not enough, then you
need adjust the valves to increase
the water flow through the heat
pump.
Must not have Valves open Full.
49