Correct Use; Inappropriate Use; Product Description Of Hand Pump - CEM DT-Mobil Serie Manual De Instrucciones

Sistema de depósito de diésel móvil
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

GB

1.2 Correct use

The DT-Mobil mobile diesel filling station is an
approved IBC (Intermediate Bulk Container) in
accordance with ADR for hazardous goods in pack-
aging group III (low-hazard liquid, water-polluting
substances).
The filling station is intended for use at a variety of
locations outdoors.
It may only be filled or transported having under-
gone a valid inspection/check. Repeat inspection
2½ years after the date of manufacture according to
ADR 6.5.4.4.1 b) and 6.5.4.4.2. Repeat inspection
5 years after the date of manufacture according to
ADR 6.5.4.4.1 a) and 6.5.4.4.2.
Note: The inspections must be repeated at intervals
of 5 years.
The double-walled filling station is additionally
approved for use as a storage tank in accordance
with DIN 6623-2. The regulations governing fire
prevention and industrial safety must be followed!
Operating temperature range: - 10 °C to + 40 °C
Important!
i
In water conservation areas,
the single-walled filling station may
only be used with a collection tray.
Important!
i
Only a clean medium may be conveyed.
Correct use (preferably) concerns, for example,
the following liquids:
• diesel fuel.
• heating oil.
• biodiesel.
In accordance with the ADR, the following
are required for the simplified transport
of dangerous goods (< 1000 points):
• labelling (sticker) of the filling station.
• requirement to equip with a fire extinguisher (2 kg)
• carriage of supporting document
(in this case, carriage paper –
observe national exemption regulations)
(no carriage paper in Germany –
exemption 18 S)
• compliance with the so-called "1000-points rule"
in accordance with table 1.1.3.6 ADR, i.e. total
quantity per transport unit < 1000 points.
» 1 l of diesel fuel = 1 point
38
i
Important!
It is essential to read the relevant
regulations of the ADR.
1.2.1 Summary
The equipment is not intended for any other purpose.
For safety reasons, modifications are not allowed to
the filling station (except for the addition of accesso-
ries specifically provided by the manufacturer) – see
section 6. Designated use also includes compliance
with all information in these operating instructions.

1.3 Inappropriate use

i
Important!
Inappropriate use also includes failure to
observe the notices in these operating
instructions.
F u r t h e r m o r e :
• non compliance with the regulations of the ADR
and prevailing national provisions.
• storage and transport of liquids other than those
stipulated under Correct use, e.g.: petrol, bio-
ethanol, chemicals, oils (lubricating, hydraulic,
plant oils).

1.4 Product description of hand pump

The installed TP3 pump is a hand-operated pump
for the delivery and dispensing of diesel fuels and
similar materials from storage containers.
Pressure
side
Level
Suction
side
Tabla de contenido
loading

Productos relacionados para CEM DT-Mobil Serie

Este manual también es adecuado para:

Dt-mobil 400 lDt-mobil 600 lDt-mobil 980 l

Tabla de contenido