Xylem CentriPro AQUAVAR SOLO2 Manual De Instalación página 18

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Parameter
Display
Flashes
Fault Code
08
8 Blinks
09
9 Blinks
18
RED LIGHT CODES
Description
Controller Status
This information is to be used by professional installers or
qualified personnel only.
Open Lead
This fault can be caused by:
• Disconnected or broken wire between the controller and
The controller will not
restart if displaying
this fault. To clear
Verify the error by turning power to controller off for 1 minute
the fault perform
and then on. If error persists, motor and wiring between
a System Reset,
controller and motor must be checked. Turn power off for
or turn off power
5 minutes. Remove the three motor wires from the terminal
to the controller,
block. Using an ohmmeter, measure the resistance from
wait 1 minute, turn
phase to phase. A disconnected or broken wire will be
on power to the
indicated by a high resistance reading (20 ohms or higher).
controller. If fault
persists contact
installer.
Low Pressure Cut-Off This fault can be caused by:
• Pressure 20 PSI below set point for 30 seconds. May be
The controller will not
restart if displaying
this fault. To clear
the fault perform
a System Reset,
or turn off power
to the controller,
wait 1 minute, turn
on power to the
controller. If fault
persists contact
installer.
motor.
a broken pipe or tripped pressure relief valve. If 20 PSI
or more pressure drop for 30 seconds is normal for the
system, switch the Low Pressure Cut-Off protection off or
change system to prevent the pressure drop.