: Point Position (Default=0)
No point.
Between first and second digits.
Between second and third digits.
Between third and fourth digits.
Between fourth and fifth digits.
: Data Record (Default=1)
Count value is saved to memory when power is
disconnected and restored on power up.
Count value is not saved to memory when power is
disconnected.
:Reset and Set Protection (Default=0)
No Reset and Set protection.
Only Reset button protection is active.
Only Set button protection is active .
Full Protection.Reset and Set button protection is active.
: Multiplication Coefficient (Default=01.0000)
The Count value that is read from Process input,is multiplied with
this value.Parameter value can be adjusted from 00.0000 to
99.9999.If this parameter is adjusted to "01.0000" then this
parameter has no effect on Process input count,so Process value
equal to the Process input count.
: Reset Offset (Default=0)
It can be adjusted from
Process is manually reset ,count process starts from this value.
: Program Password (Default=0)
It is used for accessing to the program parameters.
It can be adjusted from
If it is
; there is no password protection while
entering to the program parameters.
If operator accesses to the program parameters by entering
"0" to
,then the operator can only see the parameter
without changing,except
to
.When
to
.