Johnson Controls SEC99 Serie Instrucciones De Instalación
Johnson Controls SEC99 Serie Instrucciones De Instalación

Johnson Controls SEC99 Serie Instrucciones De Instalación

Idiomas disponibles

Idiomas disponibles

and SEC99B UltraTube Armored Tubing
Application
!
CAUTION: Risk of Personal Injury and
Environmental Damage
Do not use the SEC99A UltraCap or SEC99B
UltraTube in applications that expose the UltraCap
or UltraTube assembly to ammonia or any other
substance that is corrosive to copper or brass.
Corrosion of the copper or brass components can
result in the discharge of refrigerant that is under
pressure, which can cause personal injury and
environmental damage.
The SEC99 Series UltraCap and UltraTube provide a
means to make pressure connections for refrigeration
and air conditioning applications. The SEC99 models
are compatible with all common noncorrosive
refrigerants. Several models and styles are available.
See Table 1.
The SEC99A UltraCap has a capillary tube that
minimizes pressure pulsation. The SEC99A UltraCap
has brass-colored flare nuts on the fitting connectors.
The SEC99B UltraTube has a 1/4 in. tube that allows
more fluid flow. The SEC99B UltraTube has
silver-colored flare nuts on the fitting connectors.
The brass-armored sleeve on all SEC99 Series
models provides resistance to abrasion and facilitates
routing, coiling, or bending of the capillary or tube. The
copper capillary or tube inside the armored sleeve
does not effuse refrigerant to the environment. Some
models have a breakaway Integral Schrader® valve
depressor in the flare fitting.
Installation
The SEC99A Ultra Cap provides a means to make
pressure connections for refrigeration and air
conditioning equipment. Inherent in all heating,
ventilating, air conditioning, and refrigeration
equipment systems is vibration caused by
compressors, fans, and other reciprocating and
rotating equipment. Vibration must be taken into
account when installing the SEC99. If you do not
address the effect of vibration and subject the capillary
to adverse vibration, the capillary will fail (break).
© 2011 Johnson Controls, Inc.
Part No. 24-7664-1857, Rev. F
SEC99A UltraCap Armored Capillary
Installation Instructions SEC99 Series
Vibration varies from equipment to equipment;
however, there are some general guidelines to follow
that help minimize the effects of vibration on the
capillary:
Install the capillary as far as possible from
reciprocating compressors. The liquid line is
recommended when making high side pressure
connections.
Install the capillary so that it moves in the same
direction as the vibration. See Figure 1.
Often damaging vibration can be dampered in a
loose coil arrangement. See Figure 2.
Sometimes two loose coil perpendicular
arrangements may be required to dampen
vibration from opposite directions. See Figure 3.
Neatly coil and secure any excess capillary where
open coil installation is not necessary.
Do not allow the coils of the capillary to rub
together or rub against any other object.
MOVEMENT
DIRECTION OF
VIBRATION
Figure 1: Incorrect SEC99 Installation
VIBRATION DAMPERING
IN LOOSE COIL
MOVEMENT
DIRECTION OF
VIBRATION
Figure 2: SEC99 Dampered Loose Coil
Arrangement
Issue Date April 1, 2011
POINT OF BREAK
TO CONTROL
www.johnsoncontrols.com
1
Tabla de contenido
loading

Resumen de contenidos para Johnson Controls SEC99 Serie

  • Página 1 SEC99. If you do not address the effect of vibration and subject the capillary to adverse vibration, the capillary will fail (break). Figure 2: SEC99 Dampered Loose Coil Arrangement © 2011 Johnson Controls, Inc. Part No. 24-7664-1857, Rev. F www.johnsoncontrols.com...
  • Página 2 Note: It may be necessary to secure the capillary to a bracket or brace to quiet the vibration. The capillary CAUTION: Risk of Environmental and may need to be secured in more than one place. Property Damage Avoid sharp bends in capillary tubes. Sharp bends can weaken or kink capillary tubes, which may result DIRECTION OF in refrigerant leaks or restrictions of flow.
  • Página 3: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls/PENN Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
  • Página 4: Sec99A Ultracap Capilar Blindado Y Sec99B Ultratube Tubo Blindado

    SEC99A UltraCap Capilar Blindado y SEC99B UltraTube Tubo Blindado Aplicación La vibración varía de equipo a equipo; sin embargo, hay algunas reglas generales que se pueden seguir PRECAUCIÓN: Riesgo de Lesión para ayudar a minimizar el efecto de la vibración en el Personal y Daño Ambiental: No use el UltraCap capilar: SEC99A ni el UltraTube SEC99B en aplicaciones...
  • Página 5 3. Use una llave de 5/8” para ajustar las tuercas tipo AMORTIGUAMIENTO DE VIBRACION EN ESPIRAL FLOJO campanas. No aplique más de 13.6 N·m (10 lb·ft) de torque. AL CONTROL MOVIMIENTO 4. Revise todos los conectores y conexiones DIRECCION DE LA respecto a fugas antes de poner al sistema en VIBRACION operación.
  • Página 6: Reparaciones Y Reemplazo

    Las especificaciones de desempeño son nominales y se apegan a normas industriales aceptables. Para toda aplicación bajo condiciones más allá de estas especificaciones, consulte a la oficina Johnson Controls más cercana. Johnson Controls, Inc. no será responsable por daños resultados por la mala aplicación o mal uso de sus productos.

Este manual también es adecuado para:

Sec99aSec99b

Tabla de contenido