Preparing
to Start
the
Pump
- Deep Wei[
[ [
I_ CAUTION ] Never run pump dry. Running pump with-
out water may cause pump to overheat, damaging seal
and possibly causing burns to persons handling pump.
Fill pump with water before starting.
I_'WARNINGINever run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding
persons handling pump.
.
Open the control valve as far as possible (see Figure
15). Then remove the priming plug from the pump
and fill the pump, fill all piping between the pump
and the well, and make sure that all
piping in the well is full. If you have also installed a
priming tee in the suction piping, remove the plug
from the tee and fill the suction piping.
Open control valve
as far as possible
and fill pump and
piping through
priming port
or priming tee.
3. Power on! Start the pump and watch the pressure
gauge. The pressure should build rapidly to 50 PSi as
the pump primes.
4. After 2 or 3 minutes, the gauge should show pres-
sure. If not, stop the pump, remove the fill plugs,
reopen the control valve, and refill the pump and
piping. You may have to repeat this two or three
times in order to get all the trapped air out of the pip-
ing. Don't forget to close the control valve each time
before you start the pump.
5. When pressure hasbuilt up and stabilized at about 50
PSI, slowly open the control valve (seeFigure 17) and let
the pressure drop until the pressuregauge needle starts to
flutter. When the needle flutters, close the valve just
enough to stop the flutter (seeFigure 17). Your pump is
now operating at its most efficient point.
B-Watch
for Pressure
Gauge
to Flutter
Figure 15: Fill Pump
280
0395
2. Replace all fill plugs and close the control valve
completely (Figure 16).
Replace all
fill plugs and
close control
valve completely,
556 0395
Figure 16: Prime Pump
C-Close
Control
Valve
until
Pressure
Stabilizes
281 0395
Figure 17: Set Control
Valve
G.
After the pump has built up pressure in the system
and shut off, check the pressure switch operation by
opening a faucet or two and running enough water
out to bleed off pressure until the pump starts. The
pump should start when pressure drops to 30 PSi and
stop when pressure reaches 50 PSi. Run the pump
through one or two complete cycles to verify correct
operation. This will also help clean the system of dirt
and scale dislodged during installation.
Congratulations
on a successful installation.
If you were unsuccessful, please refer to the
Troubleshooting section (Page 13) or call our customer
service technical staff.